- 7 -
4.2 Protection for compressor locked
IC order to stop compressor completely.
YES
YES
After 1 hour.
SYSTEM PROTECT CONTROL CYCLE
1st time
OPERATE each 7min X 10 times
COMPRESSOR 1hour STOP
OPERATE each 7min X 10 times
SYSTEM PROTECT CONTROL CYCLE
333rd time
STOP COMPRESSOR
NO
YES
8
6
7
IC cancels to stop compressor.
Normal operating?
5
After restarting, does “Stop compressor”
occure 10 times within 2 min.?
4
IC cancels to stop compressor after 10 min.
3
Does system protection cycle for 333 times?
IC orders to stop compressor for 10 min.
2
• After starting 2 sec., does IC detect
rpm < 5r/sec.?
• After starting from 2-10 sec., does PCB
detect rpm over 120r/sec.?
1
•
IC continues to stop compressor until 1 hour.
• IC indicates Self Diagnosing sign.
NO
NO
•
Normal operating.
NR-B37MV2 / NR-B41MV2