Electrical Wiring
5
●
In case that the inter-unit control wiring in the link has both 3-line and 2-line
connections:
> Set the terminating resistance with the TERMINAL pin (CN-TERMINAL) on
the outdoor unit control PCB (note, that the outdoor unit is connected by 2-line
connection).
Upon shipment the terminating resistance is set to “SHORT” (operative).
Leave one unit in short circuit condition among outdoor units in the link. Change
to OPEN for other units. For a system without link (no wiring connection
between outdoor units), do not remove the short plug.
8. Do not install the inter-unit control wiring in a way that forms a loop.
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Prohibited
Prohibited
Indoor unit
Indoor unit
9. Do not install inter-unit control wiring such as star branch wiring. Star branch wiring
causes faulty address setting.
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Branch point
Prohibited
10. If branching the inter-unit control wiring, the number of branch points should be 16 or
fewer. (Branches that are less than 1 m are not included in the total branch number.)
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
more than 1 m
more than 1 m
more than 1 m
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Branch
point
16 or fewer