75
AHU Kit – Installation Instructions – 07/2023
Electrical Wiring
5
For all models
● The external signal lines must be inserted drooped in the AHU body and protected by
a clamp with the drooping wire being close to the AHU Kit to avoid water reaching the
AHU Kit.
Inside of AHU
Blower signal and
blower protection lines
Clamp
AHU Kit
Drooping wire
Blower signal output
This fan control is usually at ON position at the time of operating, but becomes OFF in defrosting.
MAH3 generation models
PAH3 generation model
X2
l
F1
X2.1
l
F2
X2.2
l
OP3
X2.3
l
K2
X2.4
l
HU1
X2.5
l
HU2
X2.6
F2
F1
X1
External Potential: max. 250 VAC 5 A
X1: Relay (field supplied)
F2
F1
X1
X2
l
F1
X2.1
l
F2
X2.2
External Potential: max. 230 VAC 8 A
X1: Relay (field supplied)
If uninterrupted fan operation is needed and cold draft air is avoided for example by some internal
bypass etc., the defrost signal (terminals OP1 and OP2 (MAH3: X4.9 and X4.10; PAH3: X4.7 and
X4.8)) can be used with an additional field supplied relay.
Blower protection input (for MAH3 generation models only)
If a switch opens, an alarm “P01” appears on a remote controller display, and operation stops.
OP3
K2
SW1
X2
l
F1
X2.1
l
F2
X2.2
l
OP3
X2.3
l
K2
X2.4
l
HU1
X2.5
l
HU2
X2.6
OP3: Fan Alarm Signal Input
Internal potential 230 VAC
Important:
Unit will only operate if this contact is closed, otherwise error code P01 will
be displayed.