AHU Kit – Installation Instructions –
11/2021
Ventilation theory and air handling units
2
Air handling unit control by external 0–10 V signal
SET
AL1
OUT
ATU
PV
SV
ºC
ºC
PACi or ECOi/ECO G outdoor unit
Air Handling Unit Kit
0–10
V control signal
External control
system
Air Handling Unit
1 This schematic layout applies only to the advanced and medium AHU Kit versions (MAH2/PAH2/PAH3) only, because
they feature an in-built CZ-CAPBC2 interface handling the 0–10 V control. This enables various control alternatives:
●
Capacity control through external BMS via 0–10 V signal (only supported by ECOi and PACi, but not by
ECO G outdoor units)
●
Capacity control through in-built supply air or ambient temperature sensor (only available with advanced
version and only supported by ECOi and PACi, but not by ECO G outdoor units)
●
Temperature setpoint control
2 As the “light” version of the AHU Kit does not include an in-built CZ-CAPBC2 interface for handling the 0–10 V control,
this schematic layout does not apply to the “light” AHU Kit version.