24
AHU Kit – Installation Instructions –
11/2021
Product description
3
3 Product description
3.1 General description
The Panasonic AHU Kits offer a wealth of connectivity possibilities so that they can be easily inte
-
grated into many systems.
The AHU Kits are part of an on-going development process aiming at constant improvement of
the product to better meet customer demand. The new generation model, PAW-280PAH3M
(-1)
,
has been developed to connect the new PACi NX outdoor units to third party AHU systems.
However, it is also compatible with PACi outdoor units.
● Three versions available for MAH2/PAH2 generation, depending on the required
functionality (light, medium or advanced version), medium version available for PAH3
generation
● IP65 enclosure (MAH2/PAH2 and PAH3 generation) providing the possibility for
outdoor installation
● 0–10 V demand control* (included on the CZ-CAPBC2 interface)
● Easy control by BMS
*
Only available with all ECOi, PACi Elite and PACi NX units, but not with ECO G units.
Features and benefits
Depending on the AHU Kit version, the devices offer the following features and benefits:
Features and benefits
Product generation
MAH2/PAH2
PAH3
Product version
Light
Medium
Advanced
Medium
Connectable with P-LINK system.
X
X
X
X
Connectable with MD protocol system
–
–
–
X
Fan control signal from the PCB can be used for controlling the air volume of an
external fan (High/Mid/Low and LL for Th-OFF)
(Need to change the fan control circuit wiring at field.)
X
X
X
X
Defrost operation signal, Thermo-ON/OFF states output
X
X
X
X
Drain pump control
(Drain-pump and the float switch to be field-supplied)
X
X
X
–
1
Basic humidifier control output
(Humidifier to be field-supplied)
X
X
X
–
Alarm and operation output
X
X
X
X
The system is controlled by the air intake (or room return air) temperature in the same
way as a standard indoor unit. Selectable modes: Automatic / Cooling / Heating / Fan
/ Dry (equivalent to Cooling).
X
X
X
X
Easy integration into BMS or AHU control systems using demand control: 40 to 115 %
(5 % steps) of nominal current by 0–10 V input signal
–
X
X
X
Temperature set point adjustment by external control system using 0–10 V or
0–140 Ohm signal
–
X
X
X
Room supply air temperature can be controlled by the additional thermostat, its
supply air temperature sensor and the 0–10 V input signal for enhanced comfort and
efficiency
–
–
X
–
Target temperature setting based on ambient temperature with CZ-CAPBC2 interface
using 0–10 V signal
–
–
X
–
Outdoor unit quiet mode operation
–
–
–
X
2
1
Only float switch signal available, but no drain pump control signal.
2
Only possible in combination with U-71PZH3E5/8, U-100/125/140PZ(H)3E5/8 and after setting the proper parameters.
27.07.2021, JW
sorry, it changed, now also new PAH3 is IP65
03.08.2021, cH: adjusted
16.08.2021, PA:back to !P66 for PAH3
25.08.2021, cH: really?
25.08.2021, PA (phone) No, leave it at IP65 for all
02.06.2021, cH
What does “MD” stand for, and what’s the benefit of
the “MD protocol” (in brief)?
02.06.2021, JW
MD protocol is the same communication protocol
which is used in all Aquarea range and RAC prod-
ucts.
Summary of Contents for PAW-280PAH3M-1
Page 2: ...Notes ...