34
Product description
Technical data and limitations – PACi systems (cont.)
AHU Kit
PAW-280PAH2(L)
Outdoor unit
PACi Elite
1-phase
U-50PE1E5
U-60PE1E5A
U-71PE1E5A
U-100PE1E5A U-125PE1E5A U-140PE1E5A
Nominal cooling capacity
kW
5.0
6.0
7.1
10.0
12.5
14.0
Nominal heating capacity
kW
5.6
7.0
8.0
11.2
14.0
16.0
Air volume (Cooling)
Min (factory)
m³/h
480
540
720
840
1,140
1,140
Max (factory)
m³/h
780
960
1,500
1,980
2,100
2,160
Air volume (Cooling),
subject to restrictions¹
Max
m³/h
1,080
1,600
1,800
2,400
2,600
2,700
AHU DX coil heat
exchanger volume
Min (factory)
dm
3
–
–
–
1.7
1.7
1.7
Max (factory)
dm
3
1.3
1.4
1.8
2.1
2.1
2.1
AHU DX coil heat
exchanger volume,
subject to restrictions
2
Max
dm
3
1.5
1.8
2.2
3.0
3.0
3.0
Additional ref. charge kg/dm
3
0.9
0.9
0.9
0.9
0.9
0.9
Max. additional
refrigerant charge
kg
0.18
0.36
0.36
0.81
0.81
0.81
Max. pipe length
m
30
40
40
30
30
30
Max. ambient temp.
for pump down
°C
n/a
35
35
25
25
25
Heat exchanger front
area
Min
m
2
–
–
–
0.43
0.43
0.43
Max
m
2
–
–
–
0.51
0.51
0.51
Power source
V / ph / Hz 230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
Dimensions (enclosure) H x W x D
mm
278 x 278 x 180 278 x 278 x 180 278 x 278 x 180 278 x 278 x 180 278 x 278 x 180 278 x 278 x 180
Net weight
Advanced / Light
kg
4.25 / 4.53
4.25 / 4.53
4.25 / 4.53
4.25 / 4.53
4.25 / 4.53
4.25 / 4.53
Protection class
IP65
IP65
IP65
IP65
IP65
IP65
Piping length
Min / Max
m
3 / 30
5 / 40
5 / 40
5 / 30
5 / 30
5 / 30
Precharged length
Max
m
20
20
20
20
20
20
Additional refrigerant charge
g/m
20
50
50
50
50
50
Piping connections
Liquid pipe
Inch (mm) 1/4” (6,35)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
Gas pipe
Inch (mm) 1/2” (12,7)
5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
Intake temperature of
AHU Kit
1
Cooling (Min / Max)
°C
18 / 32 °C DB
18 / 32 °C DB
18 / 32 °C DB
18 / 32 °C DB
18 / 32 °C DB
18 / 32 °C DB
(13 / 23 °C WB) (13 / 23 °C WB) (13 / 23 °C WB) (13 / 23 °C WB) (13 / 23 °C WB) (13 / 23 °C WB)
Heating (Min / Max) °C
16 / 30 °C DB
16 / 30 °C DB
16 / 30 °C DB
16 / 30 °C DB
16 / 30 °C DB
16 / 30 °C DB
Ambient temperature
(outdoor unit)
Cooling (Min / Max)
°C
-10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB
Heating (Min / Max) °C
-20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB
AHU Kit
PAW-280PAH2(L)
Outdoor unit
PACi Elite
3-phase
U-71PE1E8A
U-100PE1E8A U-125PE1E8A U-140PE1E8A
Nominal cooling capacity
kW
7.1
10.0
12.5
14.0
Nominal heating capacity
kW
8.0
11.2
14.0
16.0
Air volume (Cooling)
Min (factory)
m³/h
720
840
1,140
1,140
Max (factory)
m³/h
1,500
1,980
2,100
2,160
Air volume (Cooling),
subject to restrictions¹
Max
m³/h
1,800
2,400
2,600
2,700
AHU DX coil heat
exchanger volume
Min (factory)
dm
3
–
1.7
1.7
1.7
Max (factory)
dm
3
1.8
2.1
2.1
2.1
AHU DX coil heat
exchanger volume,
subject to restrictions
2
Max
dm
3
2.2
3.0
3.0
3.0
Additional ref. charge kg/dm
3
0.9
0.9
0.9
0.9
Max. additional
refrigerant charge
kg
0.36
0.81
0.81
0.81
Max. pipe length
m
40
30
30
30
Max. ambient temp.
for pump down
°C
35
25
25
25
Heat exchanger front
area
Min
m
2
–
0.43
0.43
0.43
Max
m
2
–
0.51
0.51
0.51
Power source
V / ph / Hz 230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
230 / 1 / 50
Dimensions (enclosure) H x W x D
mm
278 x 278 x 180 278 x 278 x 180 278 x 278 x 180 278 x 278 x 180
Net weight
Advanced / Light
kg
4.25 / 4.53
4.25 / 4.53
4.25 / 4.53
4.25 / 4.53
Protection class
IP65
IP65
IP65
IP65
Piping length
Min / Max
m
5 / 40
5 / 30
5 / 30
5 / 30
Precharged length
Max
m
20
20
20
20
Additional refrigerant charge
g/m
50
50
50
50
Piping connections
Liquid pipe
Inch (mm) 3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
3/8” (9,52)
Gas pipe
Inch (mm) 5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
5/8" (15,88)
Intake temperature of
AHU Kit
1
Cooling (Min / Max)
°C
18 / 32 °C DB
18 / 32 °C DB
18 / 32 °C DB
18 / 32 °C DB
(13 / 23 °C WB) (13 / 23 °C WB) (13 / 23 °C WB) (13 / 23 °C WB)
Heating (Min / Max) °C
16 / 30 °C DB
16 / 30 °C DB
16 / 30 °C DB
16 / 30 °C DB
Ambient temperature
(outdoor unit)
Cooling (Min / Max)
°C
-10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB -10 / 43 °C DB
Heating (Min / Max) °C
-20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB -20 / 15 °C WB
To be continued on next page.