Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating Indoor 20 °C DB. Heating Outdoor 7 °C DB / 6 °C WB. (DB: Dry Bulb; WB: Wet Bulb).
Specifications subject to change without notice. For detailed information about ErP / Energy Labelling, please visit our websites www.aircon.panasonic.eu or www.ptc.panasonic.eu.
Accessories
PAW-VP-RTC5B-VRF
Tank Controller for ECOi system
PAW-VP-VALV-160
Expansion valve kit 16 kW
Accessories
PAW-VP-VALV-280
Expansion valve kit 28 kW
1) Heating of sanitary water up to 55 °C with inlet air temperature at 7 °C, humidity at 89 % and inlet water temperature at 10 °C. According to EN16147. 2) Heating of sanitary water up to 55 °C with inlet air
temperature at 15 °C, humidity at 74 % and inlet water temperature at 10 °C. According to EN16147.
This product is designed to meet the European Drinking Directive 98/83/EC amended by 2015/1787/EU. The lifespan of the product is not guaranteed in the case of the use of groundwater, such as spring water
or well water, the use of tap water when salt or other impurities are contained, nor in areas of acidic water quality. Maintenance and warranty costs related to these cases are the customer’s responsibility.
* When connected as pressurised, safety valve is mandatory.
PRO-HT Tank
PAW-VP750LDHW-1
PAW-VP1000LDHW-1
Outdoor unit
U-16MF3E8
U-16MF3E8
Volume
L
726
933
Height
H x W
mm
1 855 x 990
2 210 x 990
Connections to the water supply network
1 1/4"
1 1/4"
Net weight / with water
kg
179 / 929
191 / 1 121
Nominal electrical power
kW
5,12
6,14
Reference tapping cycle
2XL
2XL
Energy consumption by chosen cycle A7 / W10-55
kWh
4,14
5,10
Energy consumption by chosen cycle A15 / W10-55
kWh
3,50
4,61
COP DHW (A7 / W10-55) EN 16147
1)
5,29
4,81
COP DHW (A15 / W10-55) EN 16147
2)
7,01
5,32
Standby input power according to EN16147
W/h
77
80
Sound pressure at 1 m
dB(A)
52
52
Average insulation thickness
mm
100
100
Heat exchanger connection for inlet / outlet
Inch (mm)
1/2 (12,70) / 3/4 (19,05)
1/2 (12,70) / 3/4 (19,05)
Maximum power consumption without heater
kWh
20,4
20,4
Maximum power consumption with heater
kWh
26,4
26,4
Number of electrical heaters x power
W
1 x 6 000
1 x 6 000
Voltage / Frequency
V / Hz
400 / 50
400 / 50
Electrical fuse rating
A
16
16
Moisture protection
IP 24
IP 24
Maximum pipe length
m
50
50
Elevation difference (in/out)
m
30/30
30/30
Operating range - outdoor temperature
°C
-20 ~ +35
-20 ~ +35
Maximum water temperature (heat pump)
°C
65
65
Maximum water temperature (electrical heater)
°C
85
85
Refrigerant (R410A) / CO
2
Eq.
kg / T
8,3 /17,1
8,3 /17,1
HIGH
PERFORMANCE
6,70
COP
DHW
OPERATION RANGE
-20°C
HIGH
TEMPERATURE
65°C
OUTPUT WATER
PRO-HT Tank DHW
Enjoy an efficient DHW and heating and cooling tank.
Panasonic commercial PRO-HT Tank solutions meet all
needs of your hot water applications providing maximum
water temperature 65 °C.
High temperature hot water is efficiently produced
without any boosters.
Can be combined with ECOi 3-Pipe to adapt various
projects from high-end residentials to offices and hotels.
Technical focus
· Water volume 750 L and 1 000 L
· Maximum hot water production 65 °C without boosters
· Heating coil 52 m (750 L) and 63 m (1 000 L)
· Tank material 3 mm
· ABS external case
NEW — VRF SYSTEMS
305
R410A