9
2.2.2 Selection of Electrical Wiring
The recommended wiring size is shown in the table 2-3.
Type of Unit
Window & Commercial Type Unit
Split Type (Separate Type)
Table 2-3 SELECTION OF ELECTRICAL WIRING
Starting
current (A)
Size of electrical wire
(
mm
2
)
Remark
①
or Remark
①
+
②(
heat-resistance Temperature:
60°C[140°F]: min.
)
Remark
③(
heat-
resistance
Temperature:
120°C[248°F]
min.
)
5m max. 10m max.
15m max.
20m max.
30m max.
50m max.
1m max.
20max.
2.0
2.0
2.0
3.5
5.5
8.0
2.0
30max.
↑
↑
3.5
5.5
↑
14.0
↑
40max.
↑
3.5
5.5
↑
8.0
↑
↑
50max.
↑
↑
↑
8.0
14.0
22.0
↑
60max.
↑
5.5
↑
↑
↑
↑
↑
70max.
3.5
↑
8.0
14.0
↑
↑
3.5
80max.
↑
↑
↑
↑
22.0
30.0
↑
90max.
↑
↑
14.0
↑
↑
↑
↑
100max.
↑
8.0
↑
↑
↑
38.0
↑
110max.
↑
↑
↑
↑
↑
↑
↑
120max.
5.5
↑
↑
22.0
30.0
↑
↑
140max.
↑
14.0
↑
↑
↑
50.0
5.5
160max.
↑
↑
22.0
↑
↑
↑
↑
180max.
↑
↑
↑
↑
38.0
60.0
8.0
200max.
8.0
↑
↑
30.0
↑
↑
↑
220max.
↑
↑
↑
↑
50.0
80.0
↑
240max.
↑
↑
↑
↑
↑
↑
14.0
CAUTION OF GROUNDING:
The internal motor protector cannot protect the compressor against all possible failures.
Please be sure that the system utilizes the grounding connection when is installed in the field.
①
Power
terminal
compresso
indoor
③
①
②
③
①
Power
source
terminal
plate
compressor
indoor
③
compressor
indoor
Power
source
terminal
plate