© Panasonic Industrial Devices SUNX Co., Ltd. 2014
60
Wiring
<In case of using I/O circuit for NPN output with SF4B-□CA-J05>
Gray cable
with black line
Gray cable
K1
K2
*S1
24V DC
±10%
+
-
Receiver
Emitter
(Brown) +V
(Brown) +V
(Pale purple) Interlock setting input
(Pink) Emission halt input / Reset input
(Yellow) Override input
(Yellow-green / Black) Auxiliary output
(Shield) Output polarity setting wire
(Shield) Output polarity setting wire
(Blue) 0V
(Blue) 0V
(Orange) Synchroni
(Yellow-green) External device monitor input
(Black) Control output 1 (OSSD 1)
(White) Control output 2 (OSSD 2)
(Orange) Synchroni
(Orange / Black) Synchronization -
(Orange / Black) Synchronization -
(Red) Muting auxiliary output
(Gray) NC
(Gray) NC
(Gray / Black) Large multi-purpose indicator input (Emitter side)
(Gray / Black) Large multi-purpose indicator input (Receiver side)
(Sky-blue / White) Muting input A
(Sky-blue / Black) Muting input B
Interlock function
Invalid (Auto-reset)
External device monitor function Invalid
Auxiliary output
Cannot be used
The device output is selected depending on the connecting state of the output polarity setting wire
(shield). Incorrect wiring may cause the lockout state.
* Symbols
Switch S1
0 to +1.5V (source current 5mA or less): Emission, Open: Emission halt
K1, K2: Safety relay unit etc.