Function
●
Interlock setting changing function
It is selectable one interlock state among the following three interlock settings.
•
Start / Restart interlock
The device goes into the interlock state after the power is turned ON, or when the light is
blocked.
The factory setting is start / restart interlock.
•
Start interlock
The device goes into the interlock state when the power supply is turned ON. Once this
interlock is reset, the device does not go into the interlock state.
•
Restart interlock
The device does not go into the interlock state when turning ON the power supply. Only
when the control output (OSSD 1 / 2) becomes ON and the light is blocked after the power
is turned ON and this device receives the light, the device goes into the interlock state.
●
External device monitor setting changing function
The setting of the external device monitor is changeable.
1. Allowable time for response time: 100 to 600ms (Unit: 10ms)
Factory setting is 300ms.
2. The external device monitor function can be selected to valid or invalid.
The factory setting is set to valid for the external device monitor function.
●
Muting setting changing function (For SF4B-□CA-J05 only)
The setting of the muting function is changeable.
1. Input order of the muting input A and B can be specified so that the muting function will be
valid.
The muting function will be valid either the muting input A or B comes first to input at the
time of factory setting.
2. Select either to validate or invalidate the muting function per beam channel. (Note 1)
The muting function is valid in all beam channels at the time of factory setting.
3. Invalidate the muting indicator diagnosis function when using the muting function. (Note 2, 3)
4. Output operation of a muting sensor which is to be connected to the muting input of this
device can be set with the handy controller (
SFB-HC
) (optional). (Note 4, 5)
•
NONO (Normally Open, Normally Open)
It is at the time of factory setting.
•
NONC (Normally Open, Normally Closed)
Connect a sensor or switch whose output operation is NO (Normally Open) type to the
muting input A and connect a sensor or switch whose output operation is NC (Normally
Closed) type to the muting input B.
To make the muting function valid, time difference between the time during muting input
A becomes ON from OFF (Open) and the time during muting input B becomes OFF
(Open) from ON should be within 3 sec.