Functions
© Panasonic Industrial Devices SUNX Co., Ltd. 2017
100
3-1 Self-Diagnosis Function (Common for all cables)
The device includes a self-diagnosis function.
Self-diagnosis is executed when the power is turned ON and periodically during operation.
If an abnormality is detected, the device is immediately put in the lockout state and the control
output (OSSD 1 / 2) is fixed in the OFF state.
Refer to
to remove the cause of the problem.
3-2 Interlock Function (8-core cable, 12-core cable)
The interlock function prevents the control output (OSSD 1 / 2) from automatically turning ON
when the device is in the light-receiving state.
With manual reset selected and the control output (OSSD 1 / 2) in the OFF state (interlock
state), execute a reset in the light-receiving state to turn ON the control output (OSSD 1 / 2).
Manual reset / automatic reset can be selected by means of the connection of the interlock set-
ting input wire (pale purple) when the power is turned ON.
Interlock setting input wire (Pale purple)
Interlock function
When using PNP output: Connect to +V
When using NPN output: Connect to 0V
Manual reset
Open
Auto reset
WARNING
●
Always verify that nobody is in the danger zone before using the interlock function.
Risk of death or serious injury.
●
Install the reset switch in a location that allows operation from outside the danger zone and
which provides a clear view of the entire danger zone.
●
When using the device with auto-reset, use a safety relay unit or other device to prevent auto-
matic restart of the system after safety output shutoff. (EN 60204-1)
Summary of Contents for SF4D-x-01 Series
Page 2: ... Panasonic Industrial Devices SUNX Co Ltd 2017 2 MEMO ...
Page 126: ...Functions Panasonic Industrial Devices SUNX Co Ltd 2017 126 MEMO ...
Page 130: ...Maintenance Panasonic Industrial Devices SUNX Co Ltd 2017 130 MEMO ...
Page 140: ...Troubleshooting Panasonic Industrial Devices SUNX Co Ltd 2017 140 MEMO ...
Page 174: ... Panasonic Industrial Devices SUNX Co Ltd 2017 174 MEMO ...