Adjustment
© Panasonic Industrial Devices SUNX Co., Ltd. 2017
90
●
Receiver indicator operation 5
<Conditions: Optical synchronization (frequency 1), Test input function valid, Interlock function invalid>
Receiver
Light blocked state
Light received state (all beam channels)
Top end beam channel
Unstable
light recep-
tion state
Stable light reception state
Light
blocked
Light
received
Light
blocked
Light
received
Bottom end beam
Received light intensity
Light
blocked
Light
blocked
Light
received
Light
received
Other beam channels
Level 1
Level 1
Level 2
Level 3
Light received
/ Light blocked
Light received
/ Light blocked
Light received
/ Light blocked
Light
blocked
Control output
(OSSD 1 / 2)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Upper application
indicator (Note 1)
Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Lower application
indicator (Note 1)
Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Stable light re-
ception indicator
Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Digital indicator
Yellow c
lights
Yellow c
lights
Yellow c
lights
Yellow c
lights
Yellow c
lights
Yellow c
lights
Yellow c
lights
Yellow c
lights
Frequency
indicator
Lights
orange
Lights
orange
Lights
orange
Lights
orange
Lights
orange
Lights
orange
Lights
orange
Lights
orange
Function setting
indicator (Note 2)
Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
Interlock
indicator
Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF Turns OFF
OSSD indicator
Lights red Lights red Lights red Lights red Lights red Lights red Lights red Lights red
Notes: 1) The states of the upper application indicator and lower application indicator can also be checked from
the side of the device.
2) The function setting indicator (yellow / orange) lights yellow when the blanking function or parallel con-
nection is used, and blinks orange when the communication module
SF4D-TM1
(option) is connected.
Summary of Contents for SF4D-x-01 Series
Page 2: ... Panasonic Industrial Devices SUNX Co Ltd 2017 2 MEMO ...
Page 126: ...Functions Panasonic Industrial Devices SUNX Co Ltd 2017 126 MEMO ...
Page 130: ...Maintenance Panasonic Industrial Devices SUNX Co Ltd 2017 130 MEMO ...
Page 140: ...Troubleshooting Panasonic Industrial Devices SUNX Co Ltd 2017 140 MEMO ...
Page 174: ... Panasonic Industrial Devices SUNX Co Ltd 2017 174 MEMO ...