background image

II - 37

 Checking the operation of the auto-

fl

 ap

(This is not available for the perimeter type, built-in type, ceiling embedded type, outdoor air processing unit with 
direct-expansion coil, and water heat exchanger unit.)

 Press the 

 button and check that the 

fl

 ap operates.

  Every time the 

 button is pressed the air direction changes.

   If the 

fl

 ap is set to the lowest setting and the 

 button pressed once more, “ 

 ” is displayed and the 

fl

 ap 

moves.

*  The wall mounted and 

fl

 oor mounted types only have the swing function, each time the 

 button is pressed 

“ 

 ” lights up or turns off.

 Checking the temperature setting

Press the remote controller temperature setting buttons, 

 and 

 , to check the temperature setting 

range display.

Upper limit

Lower limit

AUTO

27

17

HEAT

26 (35)

16 (55)

DRY/COOL

30 (5)

18 (15)

*Temperature setting cannot be performed in FAN mode.
* The numerical values in ( ) indicate the cold/hot water setting temperature of the water heat exchanger unit. 

 After the above checks have been completed, turn off all the remote controllers.

<Test run from the indoor unit>
When doing a test run from the indoor unit, it is possible to carry out settings from the remote controller.

 After pressing the remote controller 

 button for longer than 4 seconds, press the 

 button.

“Test run” is displayed on the remote controller.

 A test run can be carried out from the remote controller for up to 1 hour.

 The temperature cannot be adjusted in test run mode.

 

  Do not use test run mode other than when performing a test run, because it places a burden on the equipment.

 The test run is to be performed using either “HEAT” or “COOL” modes.

Note: For 3 minutes after turning the power on and turning the power off, the outdoor unit cannot be used.

 If normal operation is not possible, a sign is displayed on the liquid crystal display of the remote controller.
 After completion of the test run, press the remote controller 

 button again.

The “Test run” display on the remote controller turns off.

W̲02̲32-37.indd   37

W̲02̲32-37.indd   37

2012/05/22   11:24:57

2012/05/22   11:24:57

Summary of Contents for U-16GE2E5

Page 1: ...s Heat Pump Air Conditioner Applicable Models 2WAY MULTI W MULTI U 16GE2E5 U 16GEP2E5 U 20GE2E5 U 20GEP2E5 U 25GE2E5 U 25GEP2E5 U 30GE2E5 Reference No SM7110029 01 COVER indd 1 COVER indd 1 2012 09 06...

Page 2: ...e operation 1 Preparations for operating the outdoor unit II 11 3 Setting the address 1 Setting the indoor unit addresses automatically II 22 2 Setting the indoor unit addresses manually II 25 3 Check...

Page 3: ...W S 710WX2E5 71 kW 80 kW Note 1 When connecting a mixture of an outdoor air processing unit with direct expansion coil and a Multi indoor unit or connecting multiple units and just an outdoor air proc...

Page 4: ...talled by itself is 24 units or fewer d Ranges for Refrigerant Tubing Length and Installation Height Difference Category Symbol Description Tubing length m Allowable tubing length L1 Max allowable tub...

Page 5: ...Liquid tube mm 9 52 9 52 12 7 12 7 15 88 15 88 19 05 19 05 22 22 1 Select a diameter for the main tubing after a branch that is no larger than that of the header In cases where the main tubing after a...

Page 6: ...y Note 2 Leakage pressure rating must be at least 4 15 MPa 1 Select a size that does not exceed header size 2 Even for 5 6 kW or less if the indoor unit tubing branches use 15 88 mm diameter gas tube...

Page 7: ...anch points If the tube diameter at the ball valve is smaller than that of the main tube after branching install reducers only at the ball valve connections Caution When installing outdoor tubing incl...

Page 8: ...Leak detection liquid Appropriate quantity Step ladder 1 Socket wrench 1 set Cloth Appropriate quantity For wiping the leak detection liquid Ordinary tools 1 set Measurement equipment Insulation resi...

Page 9: ...g the performance settings 2 Checking the outdoor unit performance Checks before start up of the engine Test run mode settings Checking engine performance Checking for abnormal noise or vibration 3 Ne...

Page 10: ...Storage location Remarks Instruction manual These items are all stored in a plastic bag which is attached to the inside of the face panel with the display window for the operation time Explain how to...

Page 11: ...e values in M unit infinite Yes 2 1 No 1 2 1 2 Because the indoor outdoor control wiring has a ground fault search for the location of the ground fault 2 Short circuit check 2 1 Measure the resistance...

Page 12: ...the location of the connection failure between units If the device contains operation wire branched from indoor outdoor control wire there may be failure in the indoor outdoor control wire before bra...

Page 13: ...stor present Measure resistance between the ground screw and terminal board 1 Measure resistance between the ground screw and terminal board 2 Standard If there is resistance a sensor ground fault has...

Page 14: ...same wire for the signal wires and power supply wires Figure 3 7 Do not use a multi core wire for a set of signal wires Figure 4 8 Wiring a A bus system shall basically be used for multiple systems F...

Page 15: ...uipment iii Keep the separation distance at 300 mm or more from other power line cables iv If the above cables are run within the separation distance mentioned above place either one of the cable in a...

Page 16: ...te controller Remote controller Remote controller No remote controller No remote controller Group control Controller Outdoor unit 1 Indoor unit Remote controller Indoor unit Indoor unit Indoor unit In...

Page 17: ...is not considered a branch No remote controller Controller Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Do not connect more than 3 wires to a single branch point Controller Outdoor uni...

Page 18: ...ved Caution Operating the indoor unit while a securing part is attached may result in the generation of an abnormal noise and the operation of a protection device Figure 12 Remove the securing part Co...

Page 19: ...07 key to select the item To change a setting value use the UP S005 or DOWN S006 key to display a value and then press the SET S007 key to confirm the value If the SET S007 key is pressed for 1 second...

Page 20: ...ed label to the prescribed posi tion for the PL NAME Setting the fuel gas type Check that the fuel adjustment valve setting has been set before operating the outdoor main board Press the HOME S004 key...

Page 21: ...AS 04 Band Natural Gas GAS 05 No Use GAS 06 No Use GAS 07 No Use GAS 08 No Use GAS 09 No Use GAS 0A No Use GAS 0b No Use GAS 0C No Use GAS 0d No Use GAS 0E Band LNG Natural Gas GAS 0F No Use After com...

Page 22: ...setting mode Example 2012 in the example b Each press of SET S007 confirms the setting and changes the indication for the 1st digit and the setting item becomes as shown in the table The indication fo...

Page 23: ...s startup etc Display Function DOWN UP System address setting Outdoor unit address setting Only change this when connecting multiple W MULTI outdoor units Number of outdoor units connected setting Onl...

Page 24: ...key to select the connection number The indication becomes as shown below Setting range W MULTI From 1 to 2 units Indication Meaning DOWN key S006 UP key S005 on 01 Number of outdoor units connected 1...

Page 25: ...s installed Indication Meaning DOWN key S006 UP key S005 in 01 Number of indoor units connected 1 in 02 Number of indoor units connected 2 in 48 Number of indoor units connected 48 After completing th...

Page 26: ...S007 for longer than 1 second The red LED D052 lights up indicating a TEST WARNING In this condition use the UP S005 or DOWN S006 key to select the outdoor system address The display is as below The...

Page 27: ...ddress The display is as below The setting range is from 1 2 Display Meaning DOWN key 006 UP key 005 Sub 01 Outdoor unit address 1 Sub 02 Out door unit address 2 After completing selection of the outd...

Page 28: ...e left counterclockwise by 90 degrees Figure 15 Same for the gas tube liquid tube and balance tube The valve is fully open when the tab has been rotated 90 degrees when it contacts the stopper Do not...

Page 29: ...not start up while the switch is set to STOP The indication on the seven segment display changes from to the normal display CAUTION If the unit is operated while the valve is still closed the discharg...

Page 30: ...r unit with the smallest address See the sections on automatic address setting below Use one of the following methods to set the addresses of indoor units depending on the wiring of the power supply O...

Page 31: ...nd to complete the setting operation When the power cannot be turned on for each individual refrigerant tubing system In this case automatic address setting is carried out with the indoor and outdoor...

Page 32: ...lay the menu item number p Next press the UP S005 or DOWN S006 key to select the menu item number q After is displayed is displayed While is displayed press the SET S007 key Green LED lights up r Next...

Page 33: ...e Carry out the following operations from the remote controller Remote controller System address setting Press the button the button and the button simultaneously for longer than 4 seconds On the remo...

Page 34: ...ng the time setting or button set Individual when the indoor unit and remote controller are one to one and Main and the remainder Sub when using remote controller group control is displayed Press the...

Page 35: ...s This is carried out when it is not individually operated wired remote controller and indoor unit are connected one to one Method of checking the indoor unit address under group control This check is...

Page 36: ...efine the selected system address On the remote controller display Unit No Press the button Each time the button is pressed the indoor unit No Unit No tubing system is displayed and the fan only of th...

Page 37: ...de to Item code With the time setting or button set Setting data to the number to change the address Note For an individual remote controller if the address is duplicated the error message is displaye...

Page 38: ...current indoor unit is displayed in Setting data and fan of the displayed indoor unit starts to operate Using the button select the indoor unit address to change The fan of the selected indoor unit o...

Page 39: ...ng installation complete Set the refrigerant system address for all outdoor unit boards Can the power to each refrig erant system be turned ON OFF separately Is the outdoor unit operable The following...

Page 40: ...1 4 way valve continuous on cooling side 8 Humidifier setting 0 0 None 1 Heating dew condensation prevention control available L Cooling blower temperature setting 0 0 By model 35 35 92 92 N Heating...

Page 41: ...em number After displaying display the test run forced setting display While the status is test run forced setting display press the SET S007 key to display the indication shown in the figure below In...

Page 42: ...1 32 has one dot in the bottom right and the display screen for units 33 48 has two dots in the bottom right Refer to Figure 24 A light turns on to indicate that the thermostat of the corresponding i...

Page 43: ...that there is no error vibration in the refrigerant tubing or capillary tubes particularly during low rota tional speeds Check that there are no error vibrations due to contact between tubing fitting...

Page 44: ...d air in heating mode the fan may be either stopped or the air velocity may be at a very low velocity for several minutes after operation starts but the fan will operate at the air velocity set with t...

Page 45: ...water heat exchanger unit After the above checks have been completed turn off all the remote controllers Test run from the indoor unit When doing a test run from the indoor unit it is possible to carr...

Page 46: ...data displayed in the order shown in the table below If data display proceeds too far press the DOWN S006 key to display the necessary data and then record the data If the HOME S004 key is pressed for...

Page 47: ...0 40 to 80 38 Outdoor fan 1 0 to 108 0 to 90 39 Outdoor fan 2 0 to 108 0 to 90 41 Outdoor fan 1 revolutions min 1 0 to 700 0 to 580 42 Outdoor fan 2 revolutions min 1 0 to 700 0 to 580 44 Set coolant...

Page 48: ...UP 01 Indoor No 1 unit electric valve opening Step 64 to 350 300 to 480 02 Indoor No 1 unit intake temperature C 03 Indoor No 1 unit blow out temperature C 04 Indoor No 1 unit E1 temperature C 05 Ind...

Page 49: ...thick tubes are cold when cooling mode is selected Stopping the test run Press the HOME S004 key to display the menu item num ber Figure 27 Next press the UP S005 or DOWN S006 key to select menu item...

Page 50: ...re cannot be set during fan mode The numerical values in indicate the cold hot water setting temperature of the water heat exchanger unit AUTO Automatically cools or heats HEAT Heating operation DRY D...

Page 51: ...once more and it stops Time Each time the or button is pressed the time increases or decreases by 0 5 hours The upper limit is 72 hours the lower limit is 0 5 hours button At the set time timer operat...

Page 52: ...peration Preparing for heating When displayed the indoor unit fan is stopped or on very low speed Operation mode change control When Operation mode change control lights up after using the operation m...

Page 53: ...for maintenance Explain to the customer regarding the necessity of maintenance and how to carry them out c Gas heat pump air conditioning A gas heat pump GHP air conditioning system is a system power...

Page 54: ...ommunications failure Outdoor unit failed to receive signal from indoor unit Automatic address indoor unit does not exist Outdoor unit failed to send signal to indoor unit PCB Control Board trouble Du...

Page 55: ...frigerant high pressure switch activated Bypass valve failure Power phases reversed open phase 4 way valve lock trouble Indoor unit ceiling panel connector connection failure Refrigerant pressure too...

Page 56: ...ment 1 How to view of the outdoor main board Example In the case of the A 3 Outdoor main board reference refer to the area around the frame in the figure below W 03 1 indd 1 W 03 1 indd 1 2012 05 22 1...

Page 57: ...07 6 DOWN key S006 21 CN029 blue 7 UP key S005 22 CN014 blue 8 LEVEL LED D053 23 CN016 black 9 TEST WARNING LED D052 24 CN062 green Hot water outlet temperature 10 HOME key S004 25 CN060 blue Clutch c...

Page 58: ...r name Unit Measure ment value Measure ment value Measure ment value Branch tubing length Number of engine revolu tions min 1 High low differ ence Compressor inlet pressure MPa Insulation resistance c...

Page 59: ...operation data 6 Special instructions Unit No Degree of opening electric valve Intake temperature Discharge temperature Coil inlet temperature Coil outlet temperature 1 2 3 4 5 6 7 8 9 10 11 12 13 14...

Page 60: ...COVER indd 2 COVER indd 2 2012 05 22 11 27 40 2012 05 22 11 27 40...

Reviews: