9-15-2. Setting the outdoor unit system address
For basic wiring diagram (Set the system address: 1)
ON
1
2
8 – 10 HP
LED1
FUSE (0.5A, F500)
OC (CN500, BLU)
MOV2
(CN301, BLK)
MOV1
(CN300, WHT)
EMG (CN502, BRN)
SILENT (CN037, WHT)
PUMP DOWN (CN048)
TEMINAL (CN205, BLK)
R.C.ADD. Rotary switch
C2 (CN020, WHT)
C1 (CN021, WHT)
TEST (CN033, RED)
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
63PH (CN027, WHT)
EXCT
(CN030, RED)
RC P
(CN039, RED)
IC002
CTL2
(CN202, GRN)
CTL1
(CN203, GRN)
FUSE
(6.3A, F101)
N . P . C H E C K
(CN046, RED)
LED2
MODE (CN038)
D115
(POWER LED)
IC001
R.C.ADD. DIP switch
A.ADD (CN047)
C-CHK (CN035)
EEPROM
LED (D041 EEPROM LED)
Fig. 9-11
System address
No.
System address
10s digit
(2P DIP switch)
System address
1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = “0”)
Both OFF
ON
1
2
ON
OFF
“0” setting
1 (If outdoor unit is No. 1)
Both OFF
ON
1
2
ON
OFF
“1” setting
9-15-3. Automatic address setting from the outdoor unit
●
If the power can be turned ON separately for the indoor and
outdoor units in the system (indoor unit addresses can be
set without operating the compressor):
(1) Turn ON the indoor and outdoor unit power for refrigerant
system 1.
Press and hold the automatic address setting button
(black) for 1 second or longer at the outdoor unit where
the power was turned ON.
↓
Communication for automatic address setting begins. LED
1 and 2 on the outdoor unit control PCB blink alternately,
and turn OFF when address setting is completed.
↓
<Approximately 4 – 5
minutes are required.>
(2) Next, turn ON the power only at the indoor and outdoor
units in a different system. Press the automatic address
setting button (black) on the outdoor unit.
↓
LED 1 and 2 on the outdoor unit control PCB blink
alternately, and turn OFF when address setting is
completed. Repeat the same procedure for each system
and complete automatic address setting.
↓
(3) Operation using the remote controller is now possible.
9-15-4. Indoor unit remote controller main-sub setting
●
If a wired remote controller is used, set the wired remote
controller to “Sub”.
If 2 wireless remote controllers are used, set the wireless
PCB (DIP switch) on the second remote controller to “Sub”.
Outdoor unit control PCB
DIP switch
System address
System address rotary switch
(Set to “0” at time of shipment)
System address rotary switch
10s
20s
ON
OFF
8 – 10 HP
Big̲PAC̲eng.indb 31
2011/02/23 13:37:55
32
9-15-5. Indoor unit address setting
●
If multiple single-type units are installed in the same room,
the addresses can be set to prevent signal interference.
By coordinating the numbers of the indoor unit (wireless
PCB) and remote controller addresses, up to 6 indoor units
can be controlled independently by their respective remote
controllers.
Independent control is not possible when a simultaneous-
operation multi system is used.
●
Checking the addresses
Press the remote controller address button to display the
current address on the remote controller display.
If this address matches the indoor unit (wireless PCB)
address, the buzzer will sound.
(If ALL is set, the buzzer will always sound.)
If ALL is set, operation is possible regardless of the indoor
unit address.
Point the remote controller toward the receiver (indoor unit)
that you wish to operate, and send the operation signal.
●
Remote controller address setting
Press and hold the address button for 4 seconds or longer
to display the address on the remote controller display. The
current address starts blinking.
The address changes each time the remote controller
address button is pressed: ALL
→
1
→
2
→
3
→
...
→
6.
Set the address to match the remote controller you wish to
operate.
When the SET button is pressed, the address stops blinking
and displays for 5 seconds. The buzzer sounds if the
address matches the indoor unit.
Remote
controller
address
display
ALL
1
2
3
Indoor unit
PCB address,
DIP switch
12
3
6 5 4
3 2 1
ON
ON
OFF
Address
12
3
6 5 4
3 2 1
ON
ON
OFF
Address
12
3
6 5 4
3 2 1
ON
ON
OFF
Address
12
3
6 5 4
3 2 1
ON
ON
OFF
Address
For address switches 1, 2, and 3, turn DIP switch 1 to OFF.
For address switches 4, 5, and 6, turn DIP switch 1 to ON.
1
2
3
ON
■
E1 Type (for Link Wiring)
9-16. Caution
This unit may be used in a single-type refrigerant system
where 1 outdoor unit is connected to 1 indoor unit.
●
This test run explanation describes primarily the procedure
when using the wired remote controller.
●
If link wiring is used, set the outdoor unit system address
to allow the combination of indoor and outdoor units to be
identified. At the same time, indicate the indoor-outdoor unit
combination number in a location where it can be checked
easily (near the indoor unit nameplates). (This number will
be required for subsequent maintenance. Refer to 9-21-2, 3,
4.)
●
Request that the customer be present when the test run is
performed. At this time, explain the operation manual and
have the customer perform the actual steps.
●
Be sure to pass the manuals and warranty certificate to the
customer.
●
Check that the 220 – 240 V AC wiring is not connected to the
inter-unit control wiring connector terminal.
If 220 – 240 V AC is accidentally applied, the indoor or
outdoor unit control PCB fuse will blow in order to protect
the PCB. Correct the wiring connections, then disconnect
the 2P connectors (indoor: blue, OC) (outdoor: blue, serial
1) that are connected to the PCB, and replace them with 2P
connectors (indoor: brown, EMG) (outdoor: brown, serial 2).
If operation is still not possible after changing the brown
connectors, try cutting the varistor (black).
(Be sure to turn the power OFF before performing this work.)
8 – 10 HP
LED1
FUSE (0.5A, F500)
OC (CN500, BLU)
MOV2
(CN301, BLK)
MOV1
(CN300, WHT)
EMG (CN502, BRN)
SILENT (CN037, WHT)
PUMP DOWN (CN048)
TEMINAL (CN205, BLK)
R.C.ADD. Rotary switch
C2 (CN020, WHT)
C1 (CN021, WHT)
TEST (CN033, RED)
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
63PH (CN027, WHT)
EXCT
(CN030, RED)
RC P
(CN039, RED)
IC002
CTL2
(CN202, GRN)
CTL1
(CN203, GRN)
FUSE
(6.3A, F101)
N . P . C H E C K
(CN046, RED)
LED2
MODE (CN038)
D115
(POWER LED)
IC001
R.C.ADD. DIP switch
A.ADD (CN047)
C-CHK (CN035)
EEPROM
LED (D041 EEPROM LED)
Fig. 9-13
Address
Address
Address
Address
Address switch
Test
Remote controller
Sub On
Main Off
Outdoor unit control PCB
Big̲PAC̲eng.indb 32
2011/02/23 13:37:55
Big̲PAC̲eng.indb 33
2011/02/23 13:37:56
Big̲PAC̲eng.indb 34
2011/02/23 13:37:56
B
ig
̲P
A
C
̲e
n
g
̲m
en
tu
k
e.i
n
d
d
1
6
Big̲PAC̲eng̲mentuke.indd 16
2
0
1
1
/0
2
/2
3
1
3
:4
3
:4
2
2011/02/23 13:43:42
Summary of Contents for U-200PE1E8
Page 2: ......
Page 24: ... NOTE EN FR DE IT PT GR ES 22 ...
Page 46: ... NOTE 44 GB FR DE IT PT GR ES SUPPLEMENT ...
Page 68: ... ANMERKUNGEN 66 GB FR DE IT PT GR ES SUPPLEMENT ...
Page 90: ... PROMEMORIA 88 GB FR DE IT PT GR ES SUPPLEMENT ...
Page 112: ...EN FR DE IT PT GR ES 110 NOTAS ...
Page 134: ... Σημεıωματάριο 132 GB FR DE IT PT GR ES SUPPLEMENT ...
Page 156: ...EN FR DE IT PT GR ES 154 NOTAS ...
Page 157: ......