EN
FR
DE
IT
PT
GR
ES
4
7
1. GENERAL
This booklet briefly outlines where and how to install the
air conditioning system. Please read over the entire set of
instructions for the indoor and outdoor units and make sure all
accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Flathead
screwdriver
2.
Phillips head screwdriver
3.
Knife or wire stripper
4. Tape
measure
5. Carpenter’s
level
6.
Sabre saw or key hole saw
7. Hacksaw
8. Core
bits
9. Hammer
10. Drill
11. Tube
cutter
12. Tube flaring tool
13. Torque
wrench
14. Adjustable
wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Unit
See Table 1-1.
Table
Type
1-1
High Static Pressure Ducted E1 Type
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local
source, you will need:
1.
Deoxidized annealed copper tube for refrigerant tubing.
2.
Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 8 mm.
3.
Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring. Refer to 5. ELECTRICAL
WIRING for details.
CAUTION
Check local electrical codes and regulations before
obtaining wire. Also, check any specified instructions or
limitations.
1-4. Additional Materials Required for Installation
1.
Refrigeration (armored) tape
2.
Insulated staples or clamps for connecting wire (See your
local codes.)
3. Putty
4.
Refrigeration tubing lubricant
5.
Clamps or saddles to secure refrigerant tubing
6.
Scale for weighing
Table 1-1 (High Static Pressure Ducted E1 Type)
Part Name
Figure
Q’ty
Remarks
Special washer
8
For suspending indoor
unit from ceiling
Flare insulator
2
For gas and liquid
tubes
Drain socket
1
For drain pipe
connection
Tube
connector
8
type
1
For decreasing size
of liquid tube from
ø12.7 to ø9.52 mm
10
type
1
For increasing size of
gas tube from ø25.4
to ø28.58 mm (Not
used)*
* Used with the U-200PE1E8 outdoor unit
Table 1-2 (Outdoor Unit)
Name
Figure
Q’ty
Reducing Joint Tube
(ø19.05
→
ø25.4)
1
Joint Tube (ø19.05)
1
1-5. Tubing Size
(A) Single type
●
During tubing work, try to make both the tubing length (L)
and the difference in elevation (H1) as short as possible.
Refer to Table 1-3.
H1
Table 1-3 Tubing Data for Models (Single)
Models
Tubing Data
U-200PE1E8
U-250PE1E8
Tubing size
outer diameter
Liquid tube
mm (in.)
9.52 (3/8)
12.7 (1/2)
Gas tube
mm (in.)
25.4
Limit of tubing length (L)
(m)
100
Height
Differential of
Indoor/Outdoor
Units (H1)
Outdoor unit is
placed
higher
(m)
30
Outdoor unit is
placed
lower
(m)
30
Max. allowable tubing length at
shipment
(m)
5 – 30
Required additional refrigerant
(g/m)
40 *
80 *
Refrigerant charged at shipment
(kg)
5.3
6.5
No additional charge of compressor oil is necessary.
* If the total tubing length exceeds 30 m, charge the amount of refrigerant
as shown above in “Required additional refrigerant” for every 1 m in
excess of 30 m for outdoor units.
Single
Main tubing L
Big̲PAC̲eng.indb 7
2011/02/23 13:37:46
8
2. SELECTING THE INSTALLATION SITE
CAUTION
●
When moving the unit during or after unpacking, make
sure to lift it by holding its lifting lugs. Do not exert
any pressure on other parts, especially the refrigerant
piping, drain piping and flange parts.
●
If you think the humidity inside the ceiling might exceed
30°C and RH 80%, reinforce the insulation on the unit
body. Use glass wool or polyethylene foam as insulation
so that it is no thicker than 10 mm and fits inside the
ceiling opening.
2-1. Outdoor Unit
AVOID:
●
heat sources and exhaust fans, etc. (Fig. 2-1)
●
damp, humid or uneven locations.
DO:
●
choose a place as cool as possible.
●
choose a place that is well ventilated and outside air
temperature does not exceed maximum 45°C constantly.
●
allow enough room around the unit for air intake/exhaust and
possible maintenance. (Fig. 2-2)
●
use lug bolts or equal to bolt down unit, reducing vibration
and noise.
●
If cooling operation is to be used when the outdoor air
temperature is –5°C or below, install a duct on the outdoor
unit.
Fig. 2-1
Installation space
Install the outdoor unit with a sufficient space around the
outdoor unit for operation and maintenance.
(1) Obstructions on the left side, right side and rear side (Front
side and above the unit are opened). (Fig. 2-2)
Fig. 2-2
* Necessary space is required to unscrew on the rear side for
maintenance and if a suffi cient maintenance space is provided
on the rear side (40 cm), the space of over 15 cm is enough at
the right side.
CAUTION
1. This unit requires no additional refrigerant charge up to
tubing length 30 m. In case of more than 30 m, additional
refrigerant charge is required. Refer to Table 1-3.
2. In case of multi type installation, indoor units should be
installed within the same room. If multi type indoor units
are installed in different rooms, temperature control may
develop problems because thermostat operation must
follow the thermostat condition of 1 indoor unit only (the
main unit).
WARNING
Always check the gas density for the room in which the unit
is installed.
■
Check of limit density
When installing an air conditioner in a room, it is necessary to
ensure that even if the refrigerant gas accidentally escapes, its
density does not exceed the limit level.
If the density might exceed the limit level, it is necessary to
set up an opening between it and the adjacent room, or to
install mechanical ventilation which is interlocked with the leak
detector.
(Total refrigerant charged amount: kg)
(Min. indoor volume where indoor unit is installed: m
3
)
< Limit density 0.3 (kg/m
3
)
The limit density of refrigerant which is used in this unit is
0.3 kg/m
3
(ISO 5149).
The shipped outdoor unit comes charged with the amount of
refrigerant fixed for each type, so add it to the amount that
is charged at the field. (Refer to the unit’s nameplate for the
amount of charged refrigerant at shipment.)
Minimum indoor volume & floor area relative to the amount
of refrigerant are roughly as given in the following table.
40.5
54.0
27.0
13.5
0.0
20
10
0
30
40
60
70
80
90 100
50
67.5
81.0
94.5
108.0
121.5
135.0
148.5
162.0
175.5
189.0
202.5
216.0
229.5
243.0
256.0
270.0
m
2
m
3
15
10
5
0
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
283.5
297.0
310.5
324.0
337.5
kg
CAUTION
Pay special attention to any location, such as a basement
or recessed area, etc. where leaked refrigerant can collect,
since refrigerant gas is heavier than air.
Hot air
Exhaust fan
Out-
door
unit
Heat source
*25 cm
or more
20 cm
or more
15 cm
or more
Range below the
density limit of
0.3 kg/m³
(Countermeasures
not needed)
Range above the
density limit of 0.3
kg/m³
(Countermeasures
needed)
Total amount of refrigerant
Min. indoor volume
Min. indoor floor area
(when the ceiling is 2.7 m high)
Big̲PAC̲eng.indb 8
2011/02/23 13:37:47
Big̲PAC̲eng.indb 9
2011/02/23 13:37:48
Big̲PAC̲eng.indb 10
2011/02/23 13:37:48
B
ig
̲P
A
C
̲e
n
g
̲m
en
tu
k
e.i
n
d
d
4
Big̲PAC̲eng̲mentuke.indd 4
2
0
1
1
/0
2
/2
3
1
3
:4
3
:3
4
2011/02/23 13:43:34
Summary of Contents for U-200PE1E8
Page 2: ......
Page 24: ... NOTE EN FR DE IT PT GR ES 22 ...
Page 46: ... NOTE 44 GB FR DE IT PT GR ES SUPPLEMENT ...
Page 68: ... ANMERKUNGEN 66 GB FR DE IT PT GR ES SUPPLEMENT ...
Page 90: ... PROMEMORIA 88 GB FR DE IT PT GR ES SUPPLEMENT ...
Page 112: ...EN FR DE IT PT GR ES 110 NOTAS ...
Page 134: ... Σημεıωματάριο 132 GB FR DE IT PT GR ES SUPPLEMENT ...
Page 156: ...EN FR DE IT PT GR ES 154 NOTAS ...
Page 157: ......