82
Specifications
High Static Pressure Ducted
(Type E3)
Model Name
S-200PE3E5B
S-250PE3E5B
Power Source
220 - 230 - 240 V
~
50 Hz
Cooling capacity
kW
19.5
23.2
BTU/h
66,500
79,200
Sensible
kW
16.2
19.0
Latent
kW
3.3
4.2
Heating capacity
kW
22.4
28.0
BTU/h
76,400
95,500
Cooling electric power input
kW
0.610
0.830
Heating electric power input
kW
0.610
0.830
Sound
Pressure
level
High
dB(A)
46
47
Medium
dB(A)
44
45
Low
dB(A)
41
42
Sound
Power
level
High
dB(A)
78
79
Medium
dB(A)
76
77
Low
dB(A)
73
74
Unit Dimensions*
(H×W×D)
mm
486×1,456×916
486×1,456×916
Net weight*
kg
86
88
Operation condition temperature range
• Cooling mode : 18°C~32°C DB • Heating mode : 16°C~30°C DB
Indoor unit
OI_00_310269_all.indb 82
2018/12/20 9:19:34