2WAY SYSTEM
Remote Controller Functions
5
- 13
2. Detailed Settings Function
5
Item code
Item
Setting data
No.
Description
Automatic drain pump
operation
0000 No forced operation
0001 Forced operation for 1 minute
0060 Continuous operation
Ventilation fan operation
0000 None
0001 Ventilation fan operated by remote controller.
Wired remote controller
sensor
0000 Not used. (Body sensor is used.)
0001 Remote control sensor is used.
“Operation change
control in progress”
display
0000 Normal (displayed)
0001 Not displayed
OFF reminder function
for when weekly timer is
used
0000 None
0001 Only stop time setting is enabled.
Discharge temperature
control
0000 Discharge temperature control OFF
0001 Discharge temperature control ON
Heat exchanger
temperature for cold air
discharge
(Heat exchanger control
point for control to
prevent cold air)
0013 Control temperature 13°C
0014 Control temperature 14°C
0025 Control temperature 25°C
0026 Control temperature 26°C
Fan output switching
0000 Output linked with fan. (ON when indoor unit fan is operating.)
0001 Fan mode operation output
Drain pump delayed
start time
0000 No delayed start
0001 1 second delayed start
Except
Indoor unit
Type
U1, F2,
T1, E1
1 minute delayed start
Indoor unit
Type
U1, F2,
T1, E1
0002 2 seconds delayed start
2 minutes delayed start
0058 58 seconds delayed start
58 minutes delayed start
0059 59 seconds delayed start
59 minutes delayed start
0060 60 seconds delayed start
60 minutes delayed start
Humidifier setting
0000 Humidifier output OFF. Drain pump stopped.
0001 Humidifier output ON. Drain pump operates.
0002
Humidifier output ON. Drain pump operates for 1 minute when total humidifier
operating time reaches 60 minutes.
0003 Humidifier output ON. Drain pump stopped.
Flap operation mode
0000 Standard setting
0001 Draft reduction mode (Flap lower-limit position is shifted upwards.)
Flap swing mode
0000 Smudging reduction mode (Flap swing upper-limit position is shifted downwards.)
0001 Normal mode
0002 Draft reduction mode (Flap swing lower-limit position is upwards.)
SM830204-05_2WAY SYS.indb 13
2015/01/23 11:57:29
Summary of Contents for U-20ME1E81
Page 54: ... MEMO 1 46 ...
Page 102: ... MEMO 3 36 ...
Page 116: ... MEMO 4 14 ...
Page 177: ...201502 ...