6
- 3
1. Contents of Remote Controller
Switch Alarm Display
2WAY SYSTEM
Trouble Diagnosis
6
1.Contents of Remote Controller
Switch Alarm Display
2WAY SYSTEM
Trouble Diagnosis
ON: Blinking:
OFF:
Possible cause of malfunction
Wired
remote
control
display
Wireless
remote controller
receiver display
Operatio
n
Timer
Standby
for heatin
g
Serial
communication
errors
Mis-setting
Remote controller is detecting
error signal from indoor unit.
Error in receiving serial communication signal. (Signal from
main indoor unit in case of group control) Outdoor system
address, indoor unit address, or indoor unit address
independent/main/sub unit setting has not been made.
(Auto address is not completed.)
Error in transmitting serial communication signal.
Indoor unit is detecting error signal from remote controller and system controller.
Indoor unit is detecting error
signal from outdoor unit.
Error in receiving serial communication signal.
When turning on the power supply, the number of
connected indoor units does not correspond to the number
set. (Except R.C. address is “0.”)
Group wiring failure of indoor units in the refrigerant system
(occurring when remote controller is operated immediately
after automatic address setting)
•
•
•
<E01>
<E02>
<<E03>>
<<E09>>
<<L09>>
F05
F06
F07
F08
E04
E08
<E06>
Outdoor unit is detecting error
signal from indoor unit.
Error in receiving serial communication signal.
There is an indoor unit which does not send signals when
the power is ON.
•
•
Indoor unit address setting is duplicated.
•
Duplicated remote controller “main” setting.
•
Automatic address setting start is prohibited.
AP pin was short-circuited at time when automatic address
setting was started.
Indoor unit communication
error of group control wiring.
Error of main indoor unit in receiving serial communication
signal from sub indoor units.
During auto. address setting,
number of connected units
does not correspond to
number set.
Improper setting
Improper setting
Improper setting
Indoor unit
Number of connected indoor units is less than the number set.
Number of connected indoor units is more than the number set.
No indoor unit is connected during auto. address setting.
Main outdoor unit is detecting error signal from sub outdoor unit.
Duplicated outdoor unit address.
Improper wiring between main outdoor unit and sub-unit.
Error of sub outdoor unit in receiving serial communication
signal from main outdoor unit.
Outdoor unit serial communications failure.
Communication error between the microcomputers
Connected indoor unit is not a multi unit.
Duplication of main indoor unit address setting in group control.
Duplicated indoor unit priority (priority indoor unit).
Duplicated indoor unit priority (non-priority indoor unit) and
outdoor unit.
Indoor unit address is not set.
Capacity code of indoor unit is not set.
Mismatch of outdoor unit type.
4-way valve operation failure
Duplication of outdoor R.C. address setting.
Capacity code of outdoor unit is not set.
Group control wiring is connected to individual control indoor unit.
E12
E18
E16
E20
E15
E24
E25
E27
E29
E30
E31
<L03>
L06
L08
L05
<<L02>>
L04
L17
L18
L10
L07
Thermistor fault
Comp. No. 2 discharge gas temp. sensor (DISCH2)
Outdoor No. 1 coil gas temp. sensor (EXG1)
Outdoor air temp. sensor (TO)
Outdoor No. 1 coil liquid temp. sensor (EXL1)
Continued
Operating lamp
blinking
Heating ready lamp
blinking
Operating lamp
blinking
Heating ready lamp
blinking
Operating and heating
ready lamps blinking
simultaneously
Operating and heating
ready lamps blinking
simultaneously
F04
Comp. No. 1 discharge gas temp. sensor (DISCH1)
<<F02>>
<<F03>>
<<F10>>
<<F11>>
Indoor coil temp. sensor (E2)
Indoor coil temp. sensor (E3)
Indoor discharge air temp. sensor (BL)
Indoor suction air (room) temp. sensor (TA)
Operating and
timer lamps blinking
alternately
<<F01>>
Indoor coil temp. sensor (E1)
Mismatch in “No. of outdoor units” setting.
E26
Thermistor fault Outdoor unit
Operating and timer
lamps blinking
altemately
F22
Comp. No. 3 discharge gas temp. sensor (DISCH3)
ON: Blinking:
OFF:
Possible cause of malfunction
Wired
remote
control
display
Wireless
remote controller
receiver display
Operatio
n
Time
r
Standb
y
fo
r heatin
g
Thermistor fault Outdoor thermistor is either
open or damaged.
Compressor intake temp. sensor (SCT)
High pressure sensor failure. High pressure trouble.
Low-pressure sensor failure
Outdoor No. 2 coil liquid temp. sensor (EXL2)
Outdoor No. 2 coil gas temp. sensor (EXG2)
Temp. sensor at refrigerant gas outlet of dual-tube (SCG)
Improper wiring connections of ceiling panel.
Activation of
protective
device
Protective device in indoor
unit is activated.
Thermal protector in indoor unit fan motor is activated.
Float switch is activated.
Operation of protective function of fan inverter.
Protective device in outdoor
unit is activated.
O
2
sensor (detects low oxygen level) activated
F12
F16
F17
F24
F23
F14
<<P09>>
<<P12>>
<<P10>>
Faulty drain pump. Drain pump locked.
<<P11>>
<<P01>>
P14
Compressor thermal protector is activated. Power supply
voltage is unusual. (The voltage is more than 260 V or less
than 160 V between L and N phase.)
Incorrect discharge temperature. (Comp. No. 1)
High pressure switch is activated.
Negative (defective) phase.
DCCT overcurrent
Incorrect discharge temperature. (Comp. No. 2)
Compressor 3 (constant speed) discharge temp. trouble
High load alarm
Outdoor unit fan motor is unusual.
Inverter for compressor is unusual.
(DC compressor does not operate.)
When alarm message in other indoor units occurs in case of
group control, unalarmed state of indoor units are inoperative.
Indoor unit communication
error of group control wiring.
P02
P04
P03
P05
P20
P18
P17
P29
<P31>
P22
P16
Operating and timer
lamps blinking
alternately
Timer and heat
ready lamp blinking
alternately
Operating and heat
ready lamp blinking
alternately
1.Contents of Remote Controller
Switch Alarm Display
2WAY SYSTEM
Trouble Diagnosis
< > alarm indication: In some cases may affect the operation of other indoor units.
Abnormal device function
<< >> alarm indication: Does not affect the operation of other indoor units.
IPM trip (IPM current or temperature)
EEPROM on indoor unit PCB failure
EEPROM on the main or sub outdoor unit PCB has failed.
Protective
device
for compressor
is activated
Protective device for
compressor No. 1 is activated.
Operating and timer
lamp blinking
simultaneously
Operating and timer
lamp blinking
simultaneously
Protective device for
compressor No. 2 is activated. Compressor No. 2 current trouble (locked)
Compressor No. 2 CT sensor disconnected or short circuit
Compressor No. 2 discharge temp. sensor disconnected
Low pressure switch is activated.
Comp. No. 1 oil sensor
Oil sensor fault.
(Disconnection, etc.)
Comp. No. 2 oil sensor
Timer lamp blinking
Current is not detected when comp. No. 1 is ON.
H31
F29
F31
H12
H11
H13
H15
H06
H08
H27
Comp. No. 3 oil sensor
H28
H03
Compressor No. 1 discharge temp. sensor disconnected
H05
H01
Compressor No. 1 current trouble (overcurrent)
Compressor No. 2 current trouble (overcurrent)
Protective device for
compressor No. 3 is activated. Compressor No. 3 current trouble (locked)
Compressor No. 3 CT sensor disconnected or short circuit
Compressor No. 3 discharge temp. sensor disconnected
H22
H21
H23
H25
Compressor No. 3 current trouble (overcurrent)
SM830204-05_2WAY SYS.indb 3
2015/01/20 17:45:16
Summary of Contents for U-20ME1E81
Page 54: ... MEMO 1 46 ...
Page 102: ... MEMO 3 36 ...
Page 116: ... MEMO 4 14 ...
Page 177: ...201502 ...