6
- 8
2WAY SYSTEM
Trouble Diagnosis
6
4. 2WAY Alarm Codes
2WAY SYSTEM
Trouble Diagnosis
4. 2WAY Alarm Codes
Alarm meaning
6
-10
6
-10
6
-10
6
-11
6
-11
Outdoor unit failed to receive serial communication signals from indoor unit.
Automatic address setting start is prohibited.
Automatic address setting alarm (too few units)
Automatic address setting alarm (too many units)
No indoor units at automatic address setting.
Outdoor unit (INV) failed to receive communications from another outdoor
unit (constant-speed).
6
-11
6
-12
6
-12
Outdoor unit address setting failure (duplication)
Mismatch in outdoor unit quantity
Outdoor unit failed to receive communication from outdoor unit (main)
6
-12
Alarm code
E06
E12
E15
E16
E20
E24
E25
E26
E29
E31
Communication error between the microcomputers
6
-12
6
-13
6
-13
6
-13
6
-14
6
-14
6
-15
6
-15
6
-16
6
-17
6
-14
6
-14
Compressor 1 discharge temperature sensor trouble (DISCH1)
Compressor 2 discharge temperature sensor trouble (DISCH2)
Compressor 3 discharge temperature sensor trouble (DISCH3)
Gas temperature sensor trouble at outdoor heat exchanger 1 (EXG1)
Liquid temperature sensor trouble at outdoor heat exchanger 1 (EXL1)
Outdoor air temperature sensor trouble (TO)
Compressor intake temperature sensor trouble (SCT)
High-pressure sensor trouble
F04
F05
F22
F06
F07
F08
F12
F16
F17
F23
F24
F31
F14
6
-15
Temp. sensor at refrigerant gas outlet of dual-tube (SCG)
Low-pressure sensor trouble
Gas temperature sensor trouble at outdoor heat exchanger 2 (EXG2)
Liquid temperature sensor trouble at outdoor heat exchanger 2 (EXL2)
Outdoor unit non-volatile memory (EEPROM) trouble
6
-17
6
-18
Compressor 1 current trouble
6
-17
6
-18
6
-19
Constant speed compressor 2 overcurrent alarm
Constant speed compressor 2 lock current alarm
Compressor 1 CT sensor disconnected or short-circuit
Compressor 1 discharge temperature sensor disconnected
6
-19
6
-20
6
-21
6
-19
6
-19
6
-18
6
-18
6
-19
6
-19
6
-21
6
-21
H11
H01
H12
H03
H05
H06
H08
H13
H15
H21
H22
H23
H25
H27
H28
H31
Low-pressure switch activated
Compressor 1 oil detection sensor (connection) trouble
Compressor 2 CT sensor disconnected or short-circuit
Compressor 2 discharge temperature sensor disconnected
Compressor 3 overcurrent alarm
Compressor 3 lock current alarm
Compressor 3 CT sensor disconnected or short-circuit
Compressor 3 discharge temperature sensor disconnected
Compressor 2 oil detection sensor (connection) trouble
Compressor 3 oil detection sensor (connection) trouble
HIC trouble alarm
6
-22
6
-22
6
-23
6
-23
L04
L10
L17
L18
Outdoor system address duplication
Outdoor unit capacity not set
Outdoor unit model mismatch
4-way valve operation failure
6
-23
With types 8HP and 10HP, only one INV compressor is supplied.
With types 12HP, 14HP and 16HP, one INV compressor and one constant-speed
compressor (AC1) are supplied.
With types 18HP and 20HP, one INV compressor and two constant-speed compressors
(AC1, AC2) are supplied.
Page
2WAY SYSTEM
SM830204-05_2WAY SYS.indb 8
2015/01/20 17:45:17
Summary of Contents for U-20ME1E81
Page 54: ... MEMO 1 46 ...
Page 102: ... MEMO 3 36 ...
Page 116: ... MEMO 4 14 ...
Page 177: ...201502 ...