2WAY SYSTEM
Control Functions
-
Outdoor Unit
1
- 22
1
EEPROM setting in main outdoor unit
CODE: 2B
Setting No. XX
20
20 minutes
30
30 minutes (factory preset mode)
40
40 minutes
50
50 minutes
60
60 minutes
* The drain pump always operates when the indoor unit is thermostat ON in cooling operation.
* Once the drain pump operates, it keeps operating for 20 minutes.
In the above 2 cases, the drain pump operates by the signal of indoor PCB, not by CCU.
6-5. Discharge air temperature control
For Type F1, F2, M1, E1 indoor units, discharge air temperature is controlled from the CCU to prevent
condensation on duct surface in cooling operation. The CCU monitors and adjusts
To of indoor unit. The
adjustment is made by compressor capacity and MOV operation in the indoor unit.
*
To: Cooling (Discharge air temperature) - (Preset discharge air temperature)
Heating (Preset discharge air temperature) - (Discharge air temperature)
Situation in which indoor unit stops by discharge air temperature control
-
To
≦
-3.5deg, and this condition continues 7 minutes
-
To
≦
-2.0deg, and this condition continues (20 + XX) minutes
*The above mentioned “XX” is able to set in EEPROM of the main outdoor unit
EEPROM setting in main outdoor unit
CODE: E1
*In heating operation, this function virtually does not work because preset discharge air temperature is 50
℃
and
this is sufficiently higher than actual discharge temperature.
For preset discharge air temperature that is set in the indoor unit is able to change, refer to manual for indoor unit.
7-1. Oil Level
Oil level
Meaning
Conditions of oil
Judgement
2
Sufficient
The compressor contains sufficient oil.
There is no problem.
1
Slightly low
There will be a risk of oil shortage soon.
Confirm that oil is returned after
performing the oil recovery control
operation.
0
Extremely low The compressor oil is short against
required level for normal operation.
Confirm that oil level is recovered to the
required level after performing the oil
recovery control between systems.
At the time immediately after the oil level changes from 2 to 1, there is a specified amount of oil in the
compressor. Namely, soon after the oil level is changed to 1, the oil in the compressor is sufficient. If the oil level
“0” indication continues for more than 5 to 10 minutes, it seems short of oil in the system. Check valves related to
oil recovery operation, the refrigerant tubing and for any oil leakage.
6. Indoor Units Control from the CCU
7. Oil Control
Setting No.
XX
-20
-19
-18
-20
-19
-18
Interval of “1”
0
0 (factory preset mode)
10
10
SM830204-05_2WAY SYS.indb 22
2015/01/21 17:00:02