1
- 25
2WAY SYSTEM
Control Functions-Outdoor Unit
1
7. Oil Control
7-6. Indoor unit self oil recovery control
This control is carried out regularly when the system is in cooling mode.
-During stopped, fan or thermostat OFF condition, indoor unit expansion valve is opened regularly for 1 to 2 min-
utes regularly (at an interval of once every 2 hours.)
-During the thermostat ON, the indoor unit electronic thermostatic expansion valve is opened about 10 pulses
from the current status.
The state of the indoor unit is shown in the table below.
Type K1, K2 and D1 operates differently according to the setting.
EEPROM setting in main outdoor unit
CODE: 24
Setting No. 0
Setting No. 1
Type of
indoor unit
Mode of
indoor unit
Thermostat
ON/OFF
Pulse of MOV
Fan speed Flap Fan speed Flap
Stop
-
100 - 180
Stop
-
LL
Open
Open
Fan (only)
-
100 - 180
LL
Stop
LL
-
LL
Cooling
OFF
115 - 185
Set speed
Set speed
Stop
LL
Set speed
-
Set speed
-
-
-
-
-
-
-
-
-
ON
Present pulse + 20
L
-
L
L
L
-
K1, K2, D1
E1
Excluding
K1, K2, D1, E1
Stop
Stop
-
100 - 180
Stop
-
Stop
Fan (only)
Fan (only)
-
-
-
100 - 180
Stop
-
Stop
Cooling
Cooling
OFF
OFF
115 - 185
Set speed
-
Set speed
ON
ON
Present pulse + 20
100 - 180
100 - 180
115 - 185
Present pulse + 20
L
L
-
-
-
-
-
*MOV pulse might be a little different from the above values according to the operating condition.