3
- 16
2WAY SYSTEM
Outdoor Unit Repair Procedures
3
5. Checking for Leakage After Repair
5-2. Checking for Leakage in Refrigerant Tubing Between Indoor and Outdoor Units
Refer to the “Installation Instructions” that came with the outdoor unit.
High-pressure outlet port
(for ø7.94mm-dia connector)
Low-pressure outlet port
(for ø7.94mm-dia connector)
Gas tube service port
(for ø7.94mm-dia connector)
Type 14HP / 16HP
Nitrogen gas
Lo Hi
Manifold gauge
Liquid tube service port
(for ø7.94mm-dia connector)
Fig. 6-b
Fig. 6-c
High-pressure outlet port
(for ø7.94mm-dia connector)
Low-pressure outlet port
(for ø7.94mm-dia connector)
Liquid tube service port
(for ø7.94mm-dia connector)
Gas tube service port
(for ø7.94mm-dia connector)
Type 18HP / 20HP
Nitrogen gas
Manifold gauge
Lo
Hi
SM830204-05_2WAY SYS_new.indb 16
15/01/05 15:31:33