U-5~48MX3
Urban Multi air conditioner
4PW16235-1C
Installation manual
11
7. F
IELD
WIRING
7.1.
Internal wiring
–
Parts table
Refer to the wiring diagram sticker on the unit. The abbreviations
used are listed below:
A1P-A6P ................ Printed circuit board
BS1-5..................... Push button switch (mode, set, return, wiring
check, reset)
C1-4 ....................... Capacitor
DS1,2..................... Dip switch
E1HC~3HC ............ Crackcase heater
F1U ........................ Fuse (250 V, 5 A, B)(A4P)
F1U,2U................... Fuse (250 V, 10 A, B)(A1P)
F5U ........................ Field fuse
H1P-8P .................. Light emitting diode (service monitor - orange)
HAP ....................... Pilot lamp (service monitor - green)
K1M~3M ................ Compressor contactor (M1C~M3C)
K1R-15R ................ Magnetic relay
L1R ........................ Reactor
M1C,2C,3C ............ Motor (compressor)
M1F........................ Motor (fan)
PS .......................... Switching power supply
Q1RP ..................... Phase reversal detect circuit
R1 .......................... Resistor (current limiting)
R3-4 ....................... Resistor
R10-R133 .............. Resistor (current sensor)
R1T ........................ Thermistor (fin) (A2P)
R1T ........................ Thermistor (air) (A1P)
R2T ........................ Thermistor (suction)
R31T~33T.............. Thermistor (discharge)
R4T ........................ Thermistor (coil-deicer)
R5T ........................ Thermistor (coil-outlet)
R6T ........................ Thermistor (liquid-pipe receiver)
R7T ........................ Thermistor (oil)
S1NPH................... Pressure sensor (high)
NOTE
Procedures for charging additional refrigerant
(*)
(*)
[Additional refrigerant charge procedure]
To learn the system settings for additional refrigerant charging, refer to the
[Service Precaution] label attached on the back of the electric box lid in the
outdoor unit.
U-5~16MX3
One outdoor unit installed
(See figure 9)
1
Fully open the gas line stop valve (liquid line stop
valve and valve A above must be left fully closed)
and start the additional refrigerant charge
operation.
2
After the system is charged with a specified amount
of refrigerant, press the confirmation button (BS3)
on the P-board (A1P) in the outdoor unit to stop the
additional refrigerant charge operation.
3
Immediately restore the stop valve to the following
status. (Otherwise, the piping may burst due to
liquid seal.)
U-18~48MX3
When multiple outdoor unit installed
(See figure 9)
1
Fully open the gas line stop valve/oil-equalizing line
stop valve (liquid line stop valve and valves A and B
above must be left fully closed), start the additional
refrigerant charge operation.
2
After the system is charged with a specified amount
of refrigerant, press the confirmation button (BS3)
on the P-board (A1P) in the outdoor unit to stop the
additional refrigerant charge operation.
3
Immediately restore the stop valve to the following
status. (Otherwise, the piping may burst due to
liquid seal.)
1
Presssure reducing valve
2
Nitrogen
3
Tank
4
Siphon system
5
Measuring instrument
6
Vacuum pomp
7
Valve A
8
Gas side
9
Outdoor unit
10
Liquid side
11
Indoor unit
12
Stop valve service port
13
Charge hose
14
To indoor unit
15
Oil-equalizing line
16
Valve B
Liquid line
stop valve
Gas line stop
valve
Oil-equalizing line
stop valve
Open
Open
Close (Default
status before
delivery)
Liquid line
stop valve
Gas line stop
valve
Oil-equalizing line
stop valve
Open
Open
Open
All field wiring and components must be installed by a
licensed electrician and must comply with relevant local
and national regulations.
The field wiring must be carried out in accordance with the
wiring diagrams and the instructions given below.
Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.
This product’s reversed phase protection detector only
works when the product started up.
The reversed phase protection detector is designed to stop
the product in the event of an abnormalities when the
product is started up.
Replace two of the three phases (L1, L2, and L3) during
reverse-phase protection circuit operation.
Reversed phase detection is not performed while the
product is operating.
If there exists the possibility of reversed phase after an
momentary black out and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.