Wiring example for wiring inside unit

See figure 26.

9.

P

IPE

 

INSULATION

After finishing the leak test and vacuum drying, the piping must be
insulated. Take into account the following points:

Make sure to insulate the connection piping and refrigerant
branch kits entirely.

Be sure to insulate liquid and gas piping (for all units).

Use heat resistant polyethylene foam which can withstand a
temperature of 70°C for liquid side piping and polyethylene foam
which can withstand a temperature of 120°C for gas side piping.

Reinforce the insulation on the refrigerant piping according to
the installation environment.

Condensation might form on the surface of the insulation.

If there is a possibility that condensation on the stop valve might
drip down into the indoor unit through gaps in the insulation and
piping because the outdoor unit is located higher than the indoor
unit this must be prevented by sealing up the connections. See
figure 9.

10. C

HECKING

 

OF

 

UNIT

 

AND

 

INSTALLATION

 

CONDITIONS

Be sure to check the following:

The piping work

1

Make sure piping size is correct.

See "6.2. Selection of piping material" on page 5.

2

Make sure insulation work is done.

See "9. Pipe insulation" on page 15.

3

Make sure there is no faulty refrigerant piping.

See "6. Refrigerant piping" on page 4.

The electrical work

1

Make sure there is no faulty power wiring or loose nuts.

See "8. Field wiring" on page 10.

2

Make sure there is no faulty transmission wiring or loose nuts.

See "8. Field wiring" on page 10.

3

Make sure the insulation resistance of the main power circuit is
not deteriorated.

Using a megatester for 500 

V, check that the insulation

resistance of 2 M

 or more is attained by applying a voltage of

500 V DC between the power terminals and earth. Never use
the megatester for the transmission wiring (between outdoor
and indoor unit, outdoor and COOL/HEAT selector, etc.).

Precautions when laying power wiring

Do not connect wiring of different thicknesses to the
power terminal block. (Slack in the power wiring may
cause abnormal heat.)

When connecting wiring which is the same thickness,
do as shown in the figure below.

For wiring, use the designated power wire and
connect firmly, then secure to prevent outside
pressure being exerted on the terminal board.

Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
strip the head and make proper tightening impossible.

Over-tightening the terminal screws may break them.

See the table below for tightening torque for the
terminal screws.

Recommendations when connecting the ground

When pulling the ground wire out, wire it so that it comes
through the cut out section of the cup washer. (An
improper ground connection may prevent a good ground
from being achieved.) (See figure 21)

1

Electric wiring

2

Wiring between units

3

Clamp to the electric box with field supplied clamps.

4

When routing out the power/ground wires from the right side:

5

When routing the remote control cord and inter-unit wiring, secure 
clearance of 50 mm or more from the power wiring. Ensure that 
the power wiring does not contact any heated sections ( 

 ).

6

Clamp to the back of the column support with field supplied 
clamps.

7

When routing out the inter-unit wirings from the opening for piping:

8

When routing out the power/ground wires from the front:

9

When routing out the ground wires from the left side:

10

Grounding wire

11

When wiring, pay attention not to detach the acoustic insulators 
from the compressor.

12

Power supply

13

Fuse

14

Earth leakage breaker

15

Ground wire

16

Unit A

17

Unit B

18

Unit C

Tightening torque (N•m)

M8 (Power terminal block)

5.5~7.3

M8 (Ground)

M3 (Inter-unit wiring terminal block)

0.8~0.97

Ambient temperature

Humidity

Minimum thickness

30°C

75% to 80% RH

15 mm

>30°C

80 RH

20 mm

1

Gas line stop valve

2

Liquid line stop valve

3

Service port for adding refrigerant

4

Sealing up treatment

5

Insulation

6

Indoor -outdoor interconnection piping

Be sure to insulate local pipes, as touching them can
cause burns.

Summary of Contents for U-5MX4XPQ

Page 1: ...gehandleiding Urban Multi airconditioner Nederlands Manual de instalaci n Acondicionador de aire Urban Multi Espa ol Manuale d installazione Climatizzatore Urban Multi Italiano Urban Multi E Manual de...

Page 2: ...0 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm...

Page 3: ...IT TO OUT D UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 1 2 1 2 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 F1 F2 F1 F2 1 A B C A B C 1 D...

Page 4: ...the installation manual supplied with these units for their installation 1 1 Combination The indoor units can be installed in the following range Always use appropriate indoor units compatible with R...

Page 5: ...36MX4 U 18MX4 U 18MX4 450 1440 64 U 38MX4 U 18MX4 U 12MX4 U 12MX4 475 1235 61 U 40MX4 U 10MX4 U 12MX4 U 12MX4 500 1300 64 U 42MX4 U 12MX4 U 12MX4 U 12MX4 525 1365 64 U 44MX4 U 8MX4 U 18MX4 U 18MX4 550...

Page 6: ...ak Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions...

Page 7: ...ately bears the weight of the unit NOTE Use filler cloth on the forklift arms to prevent damaging the unit If the paint on the bottom frame peels off the anti corrosion effect may decrease Do not use...

Page 8: ...n outdoor and indoor units is 90 m or more the size of the main pipes both gas side and liquid side must be increased Depending on the length of the piping the capacity may drop but even in such a cas...

Page 9: ...e 5 always referring to the installation manual delivered with the kit 4 2 Possible installation patterns and configurations The piping between the outdoor units must be routed level or slightly upwar...

Page 10: ...of straight section can be ensured Improper installation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the m...

Page 11: ...select the line branch pipe When using line branch pipe at the first branch counted from the outdoor unit side Choose from the following table in accordance with the capacity of the outdoor unit For l...

Page 12: ...nd the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p 40 m The difference between the distance of the outdoor...

Page 13: ...side stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE...

Page 14: ...ting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices input V1R Power module A4P A8P V1R V2R Power module A3P X1A X4A Co...

Page 15: ...te normally in reversed phase If you connect in reversed phase replace two of the three phases This unit has a reverse phase detection circuit If it is activated only operate the unit after correcting...

Page 16: ...ing sheathed cable 16 V 1 Electric wiring diagram Printed on the back of the electric box lid 2 Power wiring and ground wiring between outdoor units inside conduit When the wiring is routed out throug...

Page 17: ...from the indoor units must be connected to the F1 F2 In Out terminals on the PC board in the outdoor unit After installing the interconnecting wires inside the unit wrap them along with the on site re...

Page 18: ...etc Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is t...

Page 19: ...iring and field piping has been completed Refrigerant may only be charged after performing the leak test and the vacuum drying The refrigerant charge of the system must be less than 100 kg This means...

Page 20: ...nance after installation of the unit BS2 SET BS2 SET BS3 RETURN BS1 MODE When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect...

Page 21: ...ct the cooling mode or heating mode for charging Continue with the automatic charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for chargi...

Page 22: ...e remote controller When the charging amount is little the PE code may not be displayed but instead the P9 code will be displayed immediately If it is not as shown above correct the malfunction as ind...

Page 23: ...ly charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for charging in heating mode 7 Ready Press the button once within 5 minutes If the b...

Page 24: ...er malfunction code display on page 21 H1P H2P H3P H4P H5P H6P H7P w c c w w w w BS4 TEST BS4 TEST BS1 MODE LED display Default status before delivery Micro computer operation monitor Mode Ready Error...

Page 25: ...ant charging from Start of automatic charging refrigerant as explained page 18 again 11 5 Checks after adding refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant...

Page 26: ...arts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished Location of the dip switches leds and buttons Led state Throughout the manual the state of the...

Page 27: ...x Multiple outdoor unit system Master unit a a The state of the H8P multi LED in a multi system shows wich unit is the master unit w slave 1 unit c or slave 2 unit x Only the master unit is connected...

Page 28: ...l refrigerant state Perform the test operation as decribed in the paragraph Test operation procedure on page 26 In case refrigerant was added without using the leak detection function charging in cool...

Page 29: ...he unit operation from a remote controller To abort the operation press the button The unit will stop after 30 seconds 6 Close the front panel in order to let it not be the cause of misjudgement 7 Che...

Page 30: ...ystem uses R410A as refrigerant R410A itself is an entirely safe non toxic non combustible refrigerant Nevertheless care must be taken to ensure that air conditioning facilities are installed in a roo...

Page 31: ...in a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment o...

Page 32: ...5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 13 14 3 5 4 2 1 7 8 9 6...

Page 33: ...4PW28163 1...

Reviews: