Installation manual
23
U-5~18MX4XPQ
Urban Multi air conditioner
4PW28163-1
12.2. Checks before initial start-up
After the installation, check the following before switching on the
circuit breaker:
1
The position of the switches that require an initial setting
Make sure that switches are set according to your application
needs before turning the power supply on.
2
Power supply wiring and transmission wiring
Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.
3
Pipe sizes and pipe insulation
Make sure that correct pipe sizes are installed and that the
insulation work is properly executed.
4
Air tight test and vacuum drying
Make sure the air tight test and vacuum drying were completed.
5
Additional refrigerant charge
The amount of refrigerant to be added to the unit should be
written on the included "Added Refrigerant" plate and attached
to the rear side of the front cover.
6
Insulation test of the main power circuit
Using a megatester for 500
V, check that the insulation
resistance of 2 M
Ω
or more is attained by applying a voltage of
500 V DC between power terminals and earth. Never use the
megatester for the transmission wiring.
7
Installation date and field setting
Be sure to keep record of the installation date on the sticker on
the rear of the upper front panel according to EN60335-2-40.
and keep record of the contents of the field setting.
12.3. Field setting
If required, carry out field settings according to the following
instructions. Refer to the service manual for more details.
Opening the switch box and handling the switches
When carrying out field settings, remove
the inspection cover (1).
Operate the switches with an insulated
stick (such as a ball-point pen) to avoid
touching live parts.
Make sure to re-attach the inspection cover (1) into the switch box
cover (2) after the job is finished.
Location of the dip switches, leds and buttons
Led state
Throughout the manual the state of the leds is indicated as follows:
Setting the dip switches
(only in case of a heat pump unit)
Setting the push button switch (BS1~5)
Function of the push button switch which is located on the outdoor
unit PCB (A1P):
The figure shows state of the led indications when the unit is shipped
from the factory.
NOTE
Remark that during the first running period of the unit,
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.
■
Make sure that the circuit breaker on the power supply
panel of the installation is switched off.
■
Attach the power wire securely.
■
Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.
NOTE
Make sure that all outside panels, except for the panel
on the electric box, are closed while working.
Close the lid of the electric box firmly before turning on
the power.
2
1
1
Led H1~8P
2
Push button switches
BS1~BS5
3
Dip switch 1 (DS1: 1~4)
4
Dip switch 2 (DS2: 1~4)
5
Dip switch 3 (DS3: 1~2)
x
OFF
w
ON
c
Blinking
What to set with dip switch DS1
1
COOL/HEAT selector (refer to "8.7. Field line connection:
transmission wiring and cool/heat selection" on page 13)
(
= not installed = factory setting)
2~4
NOT USED
DO NOT CHANGE THE FACTORY SETTING.
What to set with dip switch DS2
1~4
NOT USED
DO NOT CHANGE THE FACTORY SETTING.
What to set with dip switch DS3
1+2
NOT USED
DO NOT CHANGE THE FACTORY SETTING.
For changing the set mode
For field setting
For field setting
For test operation
For resetting the address when the wiring is changed or
when an additional indoor unit is installed
1
2
4
3
5
OFF
BS2
SET
BS1
MODE
BS3
RETURN
BS4
TEST
BS5
RESET
H1P
H2P
H3P
H4P
H5P
H6P
H7P
MODE
TEST:
HWL:
IND
MASTER
SLAVE
L.N.O.P DEMAND
C/H SELECT
H8P
MULTI
BS1 MODE
BS2 SET
BS3 RETURN
BS4 TEST
BS5 RESET
Summary of Contents for U-5MX4XPQ
Page 33: ...4PW28163 1...