background image

Installation manual

23

U-5~18MX4XPQ

Urban Multi air conditioner

4PW28163-1

12.2. Checks before initial start-up

After the installation, check the following before switching on the
circuit breaker:

1

The position of the switches that require an initial setting

Make sure that switches are set according to your application
needs before turning the power supply on.

2

Power supply wiring and transmission wiring

Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.

3

Pipe sizes and pipe insulation

Make sure that correct pipe sizes are installed and that the
insulation work is properly executed.

4

Air tight test and vacuum drying

Make sure the air tight test and vacuum drying were completed.

5

Additional refrigerant charge

The amount of refrigerant to be added to the unit should be
written on the included "Added Refrigerant" plate and attached
to the rear side of the front cover.

6

Insulation test of the main power circuit

Using a megatester for 500 

V, check that the insulation

resistance of 2 M

 or more is attained by applying a voltage of

500 V DC between power terminals and earth. Never use the
megatester for the transmission wiring.

7

Installation date and field setting

Be sure to keep record of the installation date on the sticker on
the rear of the upper front panel according to EN60335-2-40.
and keep record of the contents of the field setting.

12.3. Field setting

If required, carry out field settings according to the following
instructions. Refer to the service manual for more details.

Opening the switch box and handling the switches

When carrying out field settings, remove
the inspection cover (1).

Operate the switches with an insulated
stick (such as a ball-point pen) to avoid
touching live parts.

Make sure to re-attach the inspection cover (1) into the switch box
cover (2) after the job is finished.

Location of the dip switches, leds and buttons

Led state

Throughout the manual the state of the leds is indicated as follows:

Setting the dip switches 

(only in case of a heat pump unit)

Setting the push button switch (BS1~5)

Function of the push button switch which is located on the outdoor
unit PCB (A1P):

The figure shows state of the led indications when the unit is shipped
from the factory.

NOTE

Remark that during the first running period of the unit,
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.

Make sure that the circuit breaker on the power supply
panel of the installation is switched off.

Attach the power wire securely.

Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.

NOTE

Make sure that all outside panels, except for the panel
on the electric box, are closed while working.

Close the lid of the electric box firmly before turning on
the power.

2

1

1

Led H1~8P

2

Push button switches 
BS1~BS5

3

Dip switch 1 (DS1: 1~4)

4

Dip switch 2 (DS2: 1~4)

5

Dip switch 3 (DS3: 1~2)

x

OFF

w

ON

c

Blinking

What to set with dip switch DS1

1

COOL/HEAT selector (refer to "8.7. Field line connection: 
transmission wiring and cool/heat selection" on page 13)

(

 = not installed = factory setting)

2~4

NOT USED
DO NOT CHANGE THE FACTORY SETTING.

What to set with dip switch DS2

1~4

NOT USED
DO NOT CHANGE THE FACTORY SETTING.

What to set with dip switch DS3

1+2

NOT USED
DO NOT CHANGE THE FACTORY SETTING.

For changing the set mode

For field setting

For field setting

For test operation

For resetting the address when the wiring is changed or 
when an additional indoor unit is installed

1
2

4
3
5

OFF

BS2

SET

BS1

MODE

BS3

RETURN

BS4

TEST

BS5

RESET

H1P

H2P

H3P

H4P

H5P

H6P

H7P

MODE

TEST:

HWL:

IND

MASTER

SLAVE

L.N.O.P DEMAND

C/H SELECT

H8P

MULTI

BS1  MODE

BS2  SET

BS3  RETURN

BS4  TEST

BS5  RESET

Summary of Contents for U-5MX4XPQ

Page 1: ...gehandleiding Urban Multi airconditioner Nederlands Manual de instalaci n Acondicionador de aire Urban Multi Espa ol Manuale d installazione Climatizzatore Urban Multi Italiano Urban Multi E Manual de...

Page 2: ...0 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm...

Page 3: ...IT TO OUT D UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 1 2 1 2 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 F1 F2 F1 F2 1 A B C A B C 1 D...

Page 4: ...the installation manual supplied with these units for their installation 1 1 Combination The indoor units can be installed in the following range Always use appropriate indoor units compatible with R...

Page 5: ...36MX4 U 18MX4 U 18MX4 450 1440 64 U 38MX4 U 18MX4 U 12MX4 U 12MX4 475 1235 61 U 40MX4 U 10MX4 U 12MX4 U 12MX4 500 1300 64 U 42MX4 U 12MX4 U 12MX4 U 12MX4 525 1365 64 U 44MX4 U 8MX4 U 18MX4 U 18MX4 550...

Page 6: ...ak Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions...

Page 7: ...ately bears the weight of the unit NOTE Use filler cloth on the forklift arms to prevent damaging the unit If the paint on the bottom frame peels off the anti corrosion effect may decrease Do not use...

Page 8: ...n outdoor and indoor units is 90 m or more the size of the main pipes both gas side and liquid side must be increased Depending on the length of the piping the capacity may drop but even in such a cas...

Page 9: ...e 5 always referring to the installation manual delivered with the kit 4 2 Possible installation patterns and configurations The piping between the outdoor units must be routed level or slightly upwar...

Page 10: ...of straight section can be ensured Improper installation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the m...

Page 11: ...select the line branch pipe When using line branch pipe at the first branch counted from the outdoor unit side Choose from the following table in accordance with the capacity of the outdoor unit For l...

Page 12: ...nd the pipes that not increase the pipe size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p 40 m The difference between the distance of the outdoor...

Page 13: ...side stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE...

Page 14: ...ting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices input V1R Power module A4P A8P V1R V2R Power module A3P X1A X4A Co...

Page 15: ...te normally in reversed phase If you connect in reversed phase replace two of the three phases This unit has a reverse phase detection circuit If it is activated only operate the unit after correcting...

Page 16: ...ing sheathed cable 16 V 1 Electric wiring diagram Printed on the back of the electric box lid 2 Power wiring and ground wiring between outdoor units inside conduit When the wiring is routed out throug...

Page 17: ...from the indoor units must be connected to the F1 F2 In Out terminals on the PC board in the outdoor unit After installing the interconnecting wires inside the unit wrap them along with the on site re...

Page 18: ...etc Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is t...

Page 19: ...iring and field piping has been completed Refrigerant may only be charged after performing the leak test and the vacuum drying The refrigerant charge of the system must be less than 100 kg This means...

Page 20: ...nance after installation of the unit BS2 SET BS2 SET BS3 RETURN BS1 MODE When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect...

Page 21: ...ct the cooling mode or heating mode for charging Continue with the automatic charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for chargi...

Page 22: ...e remote controller When the charging amount is little the PE code may not be displayed but instead the P9 code will be displayed immediately If it is not as shown above correct the malfunction as ind...

Page 23: ...ly charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for charging in heating mode 7 Ready Press the button once within 5 minutes If the b...

Page 24: ...er malfunction code display on page 21 H1P H2P H3P H4P H5P H6P H7P w c c w w w w BS4 TEST BS4 TEST BS1 MODE LED display Default status before delivery Micro computer operation monitor Mode Ready Error...

Page 25: ...ant charging from Start of automatic charging refrigerant as explained page 18 again 11 5 Checks after adding refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant...

Page 26: ...arts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished Location of the dip switches leds and buttons Led state Throughout the manual the state of the...

Page 27: ...x Multiple outdoor unit system Master unit a a The state of the H8P multi LED in a multi system shows wich unit is the master unit w slave 1 unit c or slave 2 unit x Only the master unit is connected...

Page 28: ...l refrigerant state Perform the test operation as decribed in the paragraph Test operation procedure on page 26 In case refrigerant was added without using the leak detection function charging in cool...

Page 29: ...he unit operation from a remote controller To abort the operation press the button The unit will stop after 30 seconds 6 Close the front panel in order to let it not be the cause of misjudgement 7 Che...

Page 30: ...ystem uses R410A as refrigerant R410A itself is an entirely safe non toxic non combustible refrigerant Nevertheless care must be taken to ensure that air conditioning facilities are installed in a roo...

Page 31: ...in a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment o...

Page 32: ...5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 13 14 3 5 4 2 1 7 8 9 6...

Page 33: ...4PW28163 1...

Reviews: