6. Meaning of Alarm Messages
Possible cause of malfunction
Alarm
Message
Activation of
protective
device
Protective device in indoor unit
is activated.
Thermal protector in indoor unit fan motor is activated.
<<P01>>
Improper wiring connections of ceiling panel.
<<P09>>
Float switch is activated.
<<P10>>
Operation of protective function of fan inverter.
P12
O
2
sensor (detects low oxygen level) activated.
P14
Incorrect discharge temperature. (Comp. No. 1 (INV))
P03
High pressure switch is activated.
P04
Negtive (defective) phase.
P05
Compressor running failure resulting from missing phase in the
compressor wiring, etc. (Start failure not caused by IPM or no gas.)
P16
Incorrect discharge temperature. (Comp. No. 2 (constant speed))
P17
Outdoor unit fan motor is unusual.
P22
Overcurrent at time of compressor runs more than 80Hz (DCCT
secondary current or ACCT primary current is detected at a time other
than when IPM has tripped.)
P26
IPM trip (IPM current or temperature)
H31
Inverter for compressor is unusual. (DC compressor does not operate.)
P29
Thermistor fault
Indoor thermistor is either open
or damaged.
Indoor coil temp. sensor (E1)
<<F01>>
Indoor coil temp. sensor (E3)
<<F03>>
Indoor suction air (room) temp. sensor (TA)
<<F10>>
Indoor discharge air temp. sensor (BL)
<<F11>>
Outdoor thermistor is either
open or damaged.
Comp. No. 1 (INV) discharge gas temp. sensor (DISCH1)
F04
Comp. No. 2 (constant speed) discharge gas temp. sensor (DISCH2)
F05
Outdoor No. 1 coil gas temp. sensor (EXG1)
F06
Outdoor No. 1 coil liquid temp. sensor (EXL1)
F07
Outdoor air temp. sensor (AIR TEMP)
F08
Compressor suction temp. sensor (SCT)
F12
High pressure sensor.
F16
Low-pressure sensor failure
F17
Outdoor No. 2 coil gas temp. sensor (EXG2)
F23
Outdoor No. 2 coil liquid temp. sensor (EXL2)
F24
EEPROM on indoor unit PCB failure
F29
Protective
device for
compressor is
activated
Protective device for
compressor No.1 (INV) is
activated.
EEPROM on the main or sub outdoor unit PCB has failed.
F31
Current is not detected when comp. No. 1 (INV) is ON.
H03
Protective device for
compressor No.2 (constant
speed) is activated
Overload current is detected.
H11
Lock current is detected.
H12
Current is not detected when comp. No.2 (constant speed) is ON.
H13
Discharge gas temperture of comp. No.2 (constant speed) is not
detected.
H15
Low pressure trouble
H06
Low oil level alarm.
H07
Oil sensor fault.
(Disconnection, etc.)
Comp. No.1 (INV) oil sensor
H08
Comp. No.2 (constant speed) oil sensor
H27
Continued
SM830202-00̲3WAY VRF.indb 15
SM830202-00̲3WAY VRF.indb 15
2012/01/30 14:52:36
2012/01/30 14:52:36