1
- 16
Test Run
1
2
3
4
5
6
7
8
6. Meaning of Alarm Messages
Alarm messages displayed on system controller
Serial
communication
errors
Mis-setting
Error in transmitting serial
communication signal
Indoor or main outdoor unit is not oparating correctly.
Mis-wiring of control wiring between indoor unit, main outdoor unit and
system controller.
C05
Error in receiving serial
communication signal
Indoor or main outdoor unit is not operating correctly.
Mis-wiring of control wiring between indoor unit, main outdoor unit and
system controller.
CN1 is not connected properly.
C06
Activation of
protective
device
Protective device of sub indoor
unit in group control is activated
When using wireless remote controller or system controller, in order to
check the alarm message in detail, connect wired remote controller to
indoor unit temporarily.
P30
NOTE
1. Alarm messages in << >> do not affect other indoor unit operations.
2. Alarm messages in < > sometimes affect other indoor unit operations depending on the fault.
SM830202-00̲3WAY VRF.indb 16
SM830202-00̲3WAY VRF.indb 16
2012/01/30 14:52:37
2012/01/30 14:52:37
Summary of Contents for U-72MF1U9