2
- 38
Remote Control Functions
3. Timer Remote Controller
1
2
3
4
5
6
7
8
Table 1 Table of DC Fan Motor Tap Settings (4-way Air Discharge Semi-Concealed type)
Table 2 Table of DC Fan Motor Tap Settings (ceiling-mounted type)
Table 3 Table of DC Fan Motor Tap Settings (1-way Air Discharge Semi-Concealed type)
* Failure to make this setting may result in
decreased airflow and condensation.
Selecting the DC fan motor tap (when setting with the remote controller)
<Procedure>
Stop the system before performing these steps.
Press and hold the
, and buttons simultaneously
for 4 seconds or longer.
If group control is in effect, press the
button and select the
address (unit No.) of the indoor unit to set. At this time, the
fan at the indoor unit begins operating.
Use the temperature setting buttons to select item code “5d.”
Press the timer time
/
buttons to select the desired
setting data.
*
For item codes and setting data, refer to Table 1 – Table 4.
Press the
button. (The display stops blinking and remains
lit, and setting is completed.)
*
If air-blocking material is used, use the same procedure as in steps
(3) – (5) above and change the setting for item code “62”
to “0000.” To change the selected indoor unit, go to step (2).
Press the
button to return to normal remote controller display.
Setting No. Remote controller setting data
Purpose of use, names of accessories
0000
(1) 0001
(3) 0003
(6) 0006
Standard (setting at time of shipping)
High ceiling setting 1 (for standards panel)
Super long-life filter
Oil guard panel
Oil guard panel with raising / lowering grille
Ammonia deodorant filter
Optical regeneration deodorant filter
High ceiling setting 2 (for standards panel)
Ceiling panel with special raising / lowering grille for high locations
High performance filter (90% by JIS colorimetric method)
High performance filter (65% by JIS colorimetric method)
Air cleaning unit
Optical regeneration deodorant filter for air cleaning unit
Deodorant filter
Air-blocking material (for 3-way air discharge)
Air-blocking material (when a discharge duct is connected)
Air-blocking material (for 2-way air discharge)
Setting No. Remote controller setting data
Purpose of use, names of accessories
0000
(1) 0001
(3) 0003
Standard (setting at time of shipping)
High ceiling setting
Super long-life filter
Ammonia deodorant filter (65% by JIS colorimetric method)
Optical regeneration deodorant filter
High performance filter (65% by JIS colorimetric method)
Deodorant filter (65% by JIS colorimetric method)
Setting No. Remote controller setting data
Purpose of use, names of accessories
0000
(1) 0001
(3) 0003
Standard (setting at time of shipping)
Ammonia deodorant filter (65% by JIS colorimetric method)
Deodorant filter (65% by JIS colorimetric method)
Optical regeneration deodorant filter
6
2
4
3
1
5
SM830202-00̲3WAY VRF.indb 38
SM830202-00̲3WAY VRF.indb 38
2012/01/30 14:52:55
2012/01/30 14:52:55