3
- 2
Trouble Diagnosis
1. Contents of Remote Controller Switch Alarm Display
1
2
3
4
5
6
7
8
Continued
Operating
lamp blinking
Operating
lamp blinking
Heating ready
lamp blinking
Operating and heating
ready lamps blinking
simultaneously
Operating and heating
ready lamps blinking
simultaneously
Heating ready
lamp blinking
Wired
remote
control
display
Wireless
remote controller
receiver display
ON:
Operation
T
imer
Standb
y
fo
r heating
Blinking:
OFF:
Possible cause of malfunction
Operating and timer
lamps blinking
alternately
Remote controller is
detecting error signal from
indoor unit.
Indoor unit is detecting error
signal from outdoor unit.
Outdoor unit is detecting error
signal from indoor unit.
Improper setting
Indoor unit communication
error of group control wiring.
During auto. address setting,
number of connected units
does not correspond to
number set.
Improper setting
<E01>
<E02>
E06
<<E03>>
E04
<<E08>>
<<E09>>
E12
E18
E15
E16
E20
E24
E25
E26
E29
<L03>
<<L02>>
L07
L08
<<L09>>
L17
Indoor unit is detecting error signal from remote controller and system controller.
Error in receiving serial communication signal.
(Auto address is not completed.)
Error in transmitting serial communication signal.
Group wiring failure of indoor units in the refrigerant system
(occurring when remote controller is operated immediately after
automatic address setting)
Indoor unit address setting is duplicated.
Error of main indoor unit in receiving serial communication signal
from sub indoor units.
Duplicated remote controller "main" setting.
Starting auto. address setting is prohibited.
AP pin / CN102 is shorted while the auto. address setting
started.
Number of connected indoor units is less than the number set.
Number of connected indoor units is more than the number set.
Duplicated outdoor unit address setting.
Mismatch in "No. of outdoor units" setting.
Error of sub outdoor unit in receiving signal from main outdoor
unit.
Duplication of main indoor unit address setting in group control.
Group control wiring is connected to individual control indoor unit.
Indoor unit address is not set.
Capacity code of indoor unit is not set.
No indoor unit is connected.
Main outdoor unit is detecting error signal from sub outdoor unit.
Mismatch of outdoor unit type.
Serial
communication
errors
Mis-setting
Connected indoor unit is not a multi unit.
L04
Duplication of outdoor system address setting.
Capacity code of outdoor unit is not set.
L10
Error in receiving serial communication signal.
There is an indoor unit which does not send signals when the
power is ON.
Indoor unit
Thermistor
fault
<<F01>>
<<F03>>
<<F10>>
<<F11>>
Indoor coil temp. sensor (E1)
Indoor coil temp. sensor (E3)
Indoor suction air (room) temp. sensor (TA)
Indoor discharge air temp. sensor (BL)