Outline of 3WAY VRF SYSTEM
1
- 4
8
7
6
5
4
3
2
1
2. Features of 3WAY VRF SYSTEM
System example
* Panasonic makes it possible to link outdoor
unit together for a large capacity (24-Ton).
Since all pipings are concentrated
into one pipe shaft, you can minimize
piping space and construction labor
Maximum number of combined outdoor units
Maximum actual piping length
3
24-Ton
40
50~130%
492ft
984 ft
System limitations
If the additional installment of outdoor and indoor units are
expected, the size of refrigerant piping should be decided
according to the total capacity after the addition.
Maximum tonnage of combined outdoor units
Maximum number of connectable indoor units
Indoor/outdoor unit capacity ratio
Maximum level difference (when outdoor unit is lower)
Maximum total piping length
164 (131) ft
If indoor/outdoor units need servicing, a ball
valve (field supply) cuts off non-operational
units to let other units stay running.
If your indoor capacity load changes in the future, it’s easy to
add on both indoor and outdoor units using the same pipings.
ADDITION
CONCENTRATION
CONNECTION
Solenoid
valve kit
Indoor unit
Combination of outdoor units
R407C models and R22 models must not be used in combination with each other.
The DC inverter unit can be used independently or in combination.
Total
tonnage
6
8
12
14
16
18
20
22
24
Type (ton)
6
8
1
1
1
2
2
3
1
1
2
2
3
1
2-1. Outline of 3WAY VRF SYSTEM
*
CAUTION
TD831158-00̲3WAY̲VRF̲SYS.indb 4
TD831158-00̲3WAY̲VRF̲SYS.indb 4
2012/01/23 20:13:51
2012/01/23 20:13:51