background image

12

Safety precautions

3. Repairs to sealed components

• During repairs to sealed 

components, all electrical supplies 

shall be disconnected from the 

equipment being worked upon prior 

to any removal of sealed covers, etc.

• If it is absolutely necessary to have 

an electrical supply to equipment 

during servicing, then a permanently 

operating form of leak detection shall 

be located at the most critical point 

to warn of a potentially hazardous 

situation.

• Particular attention shall be paid 

to the following to ensure that by 

working on electrical components, 

the casing is not altered in such a 

way that the level of protection is 

affected. This shall include damage 

to cables, excessive number of 

connections, terminals not made 

to original speci

fi

 cation, damage to 

seals, incorrect 

fi

 tting of glands, etc.

• Ensure that apparatus is mounted 

securely.

• Ensure that seals or sealing 

materials have not degraded such 

that they no longer serve the 

purpose of preventing the ingress of 

fl

 ammable atmospheres.

• Replacement parts shall be in 

accordance with the manufacturer’s 

speci

fi

 cations.

NOTE: The use of silicon sealant may 

inhibit the effectiveness of some types 

of leak detection equipment.

Intrinsically safe components do not 

have to be isolated prior to working 

on them.

 

4.  Repair to intrinsically safe 

components

• Do not apply any permanent 

inductive or capacitance loads to 

the circuit without ensuring that 

this will not exceed the permissible 

voltage and current permitted for the 

equipment in use.

• Intrinsically safe components are 

the only types that can be worked 

on while live in the presence of a 

fl

 ammable atmosphere.

• The test apparatus shall be at the 

correct rating.

• Replace components only with 

parts speci

fi

 ed by the manufacturer. 

Unspeci

fi

 ed parts by manufacturer 

may result ignition of refrigerant in 

the atmosphere from a leak.

5. Cabling

• Check that cabling will not be 

subject to wear, corrosion, excessive 

pressure, vibration, sharp edges or 

any other adverse environmental 

effects.

• The check shall also take into 

account the effects of aging or 

continual vibration from sources 

such as compressors or fans.

6.  Detection of 

fl

 ammable 

refrigerants

• Under no circumstances shall 

potential sources of ignition be used 

in the searching or detection of 

refrigerant leaks.

• A halide torch (or any other detector 

using a naked 

fl

 ame) shall not be 

used.

Summary of Contents for WH-ADC0509L3E5

Page 1: ...oor Unit WH ADC0509L3E5 WH ADC0509L6E5 WH ADC0509L3E5AN WH ADC0509L6E5AN Outdoor Unit WH WDG05LE5 WH WDG07LE5 WH WDG09LE5 ENGLISH Before operating the system please read these operating instructions t...

Page 2: ...up 32 42 5 1 Optional PCB connectivity 5 2 Zone Sensor 5 3 Heater capacity 5 4 Anti freezing 5 5 DHW capacity 5 6 Buffer tank connection 5 7 Base pan heater 5 8 Alternative outdoor sensor 5 9 Bivalent...

Page 3: ...Min Max 65 3 20 55 Below Ambient 20 C 4 20 75 Above Ambient 10 C 4 5 20 Outdoor ambient temperature C Min Max 25 35 10 43 When the outdoor temperature is out of the range in the table the heating cap...

Page 4: ...een given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children shall not play with the appliance Cleaning and user maintenance shall no...

Page 5: ...check RCCB ELCB operation regularly especially after installation inspection and maintenance RCCB ELCB malfunction may result in electric shock and or fire It is strongly recommended that Install Res...

Page 6: ...containers or Not immersed in water After a long period of use or use with any combustible equipment aerate the room regularly After a long period of use make sure the installation rack does not dete...

Page 7: ...thin a system is prohibited Operation maintenance repairing and refrigerant recovery should be carried out by trained and certified personnel in the use of flammable refrigerants and as recommended by...

Page 8: ...posal and c Able to understand and to apply in practice the requirements in the national legislation regulations and Standards and d Continuously undergo regular and further training to maintain this...

Page 9: ...se of flammable refrigerants Servicing shall be performed only as recommended by the manufacturer 2 2 Work Prior to beginning work on systems containing flammable refrigerants safety checks are necess...

Page 10: ...extinguisher adjacent to the charging area 2 5 No ignition sources No person carrying out work in relation to a refrigerating system shall use any sources of ignition in such a manner that it may lea...

Page 11: ...constructed of materials which are inherently resistant to being corroded or are properly protected against being so corroded 2 8 Checks to electrical devices Repair and maintenance to electrical comp...

Page 12: ...s NOTE The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment Intrinsically safe components do not have to be isolated prior to working on them 4 Repair to...

Page 13: ...requires brazing all of the refrigerant shall be recovered from the system The precautions in 8 must be followed to remove the refrigerant 8 Removal and evacuation When breaking into the refrigerant...

Page 14: ...discharging the refrigerant To avoid fire or explosion dissipate static electricity during transfer by grounding and bonding containers and equipment before charging discharging 10 Decommissioning Be...

Page 15: ...ants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders for holding th...

Page 16: ...ry cylinder and the relevant Waste Transfer Note arranged Do not mix refrigerants in recovery units and especially not in cylinders If compressors or compressor oils are to be removed ensure that they...

Page 17: ...tective zone must not extend to adjacent buildings or public traffic areas boundaries of neighbors the public road neighbor s private roads subsidence area depressions pump shafts sewers intakes waste...

Page 18: ...with white icons 4 Main Menu button For function setup 5 ON OFF button Starts Stops operation 6 Operation indicator Illuminates during operation blinks during alarm When the backlight is off press any...

Page 19: ...k is installed The direction icons point to the currently active mode Room operation Tank operation Deice operation B Operation icons The status of operation is displayed Icon will not display under o...

Page 20: ...nth Day Hour Min 12 00 am 2022 1 Select with or how to display the time either 24h or am pm format for example 15 00 or 3 00 pm 2 Press to confirm the selection 3 Use and to select year month day hour...

Page 21: ...the setting according to the instructions displayed at the bottom of the screen The icons refer to each selection key Quick Menu Force DHW Powerful Quiet Force Heater Weekly Timer Force Defrost Error...

Page 22: ...f operation mode should change back to the previous memorized status Powerful Select this icon to operate the heating cooling system powerfully Press to confirm your selection The powerful operation s...

Page 23: ...2 The Quiet mode operates at level 3 Level 3 is the most quiet mode Select this to set a timer for the Quiet mode operation After 1 sec delay Select Yes Select Yes using buttons Select pattern 1 6 Sel...

Page 24: ...lection The Force Heater mode starts approximately 1 minute after is pressed Force Heater is turned off Force Heater is turned on Note Force Heater is disabled whenever operation is already on and Dis...

Page 25: ...Select the day s which you wish to edit using buttons If all 6 patterns are not preset this screen will be displayed 1 2 3 4 5 6 1 Select pattern 1 6 2 Set the hour and minutes of the Timer 3 Select O...

Page 26: ...lock the Remote Controller Press to confirm your selection When the mode has been accepted below screen will be displayed Select Yes The Main Screen will be locked If No is selected the screen will r...

Page 27: ...p 1 1 Weekly timer Once the weekly timer is set up User can edit from Quick Menu To set up to 6 patterns of operation on a daily basis Disabled if Heat Cool SW is select Yes or if Force Heater is on T...

Page 28: ...N or OFF ON Do not use the system during sterilization in order to prevent scalding with hot water or overheating of shower Ask an authorised dealer to determine the level of sterilization function fi...

Page 29: ...y differ from value measured by precise equipment 2 2 System information Shows all system information in each area Actual system information of 11 items Inlet Outlet Zone 1 Zone 2 Tank Buffer tank Sol...

Page 30: ...RC No Confirm 10 34am Mon RC 1 3 2 Touch sound Turns the operation sound ON OFF ON 3 3 LCD contrast Sets the screen contrast 3 3 4 Backlight Sets the duration of screen backlight 1 min 3 5 Backlight i...

Page 31: ...SCH ITALIANO ESPA OL DANISH SWEDISH NORWEGIAN POLISH CZECH NEDERLANDS T RK E SUOMI MAGYAR SLOVEN INA HRVATSKI LIETUVI PORTUGU S EESTI LATVIE U ROM N SHQIP SLOVEN INA 3 9 Unlock password 4 digit passwo...

Page 32: ...Heat Cool SW 5 2 Zone Sensor To select the sensors and to select either 1 zone or 2 zone system Zone After selecting 1 or 2 zone system proceed to the selection of room or swimming pool If the swimmi...

Page 33: ...Steps 1 C Select Confirm 10 34am Mon 5 C 5 7 Base pan heater To select whether or not optional base pan heater is connected Type A The base pan heater activates only during deice operation Type B The...

Page 34: ...door temperature for turn ON Bivalent connection Yes After selecting the outdoor temperature Control pattern Alternative Parallel Advanced parallel Select advanced parallel for bivalent use of the tan...

Page 35: ...Boiler OFF Short Open Heat Pump ON Boiler OFF Open Short Heat Pump OFF Boiler ON Short Short Heat Pump ON Boiler ON To do settings related to electricity and boiler so that unit is able to determine...

Page 36: ...ity price Set the price according to value provided by electrical supply company Figure 1 Bivalent connection 10 34am Mon Select 0 0 Range 0 999 9 kWh Steps 0 1 kWh Electricity price 1 0 0 0 0 Confirm...

Page 37: ...1month Select Confirm 10 34am Mon Dec Yes Smart After selecting for the external pump Schedule Schedule setting Start time Pattern 1 3 00am Start time Pattern 2 9 00am Start time Pattern 3 4 00pm Sta...

Page 38: ...set value of Electricity price 1 to Electricity price 10 When the price is set to 0 the electricity price will be treated as 0 0 kWh It is for the convenience of installer when 0 0 is the desired set...

Page 39: ...Antifreeze temperature Yes After selecting the tank T ON temperature T OFF temperature After setting the antifreeze temperature 80 C Set Hi limit 5 12 External error signal No 5 13 Demand control No...

Page 40: ...20 Defrost signal To turn on defrost signal to stop fan coil during defrost operation If defrost signal set to yes bivalent function will not available to use No 5 21 Pump flowrate To set variable flo...

Page 41: ...tion meter is connected It is to measure energy generation of heat pump unit during heating cooling and DHW operation one generation meter system or during heating and cooling only two generation mete...

Page 42: ...E If Approx is shown on Energy Monitor display data displayed on the remote controller is obtained through heat pump s internal calculation If Approx is NOT shown on Energy Monitor display data displa...

Page 43: ...ntal X axis 2 on vertical Y axis Heat ON Water temp Zone1 Confirm Select 55 C 75 20 20 15 35 C 5 C 15 C Temperature range X axis 20 C 15 C Y axis See below Temperature range for the Y axis input WH WD...

Page 44: ...ater ON OFF Water temperature for heater ON 4 C Setting of water temperature to turn on from water set temperature Heater ON OFF Water temperature for heater OFF 2 C Setting of water temperature to tu...

Page 45: ...m is selected temperature set point must input for Zone 2 Zone 1 and Zone 2 will not appear on the display if only 1 zone system T for cooling ON 5 C Set T for cooling ON This setting will not availab...

Page 46: ...3 functions at a time Floor operation time max 8 00 Maximum time for floor operation in hours and minutes Tank heat up time max 1 00 Maximum time for heating the tank in hours and minutes Tank re heat...

Page 47: ...w rate max duty and operation ON OFF of the pump Flow rate XX X L min Max Duty 0x40 0xFE Pump ON OFF Air Purge 7 2 Dry concrete To dry the concrete floor walls etc during construction Do not use this...

Page 48: ...ngle when one remote controller is connected Select Dual when two remote controllers are connected Second remote controller can be used for zone 2 room temperature control Single Selection of one or t...

Page 49: ...and 3 0 bar In case the water pressure is out of the above range consult an authorised dealer Water pressure can be checked through following method Go to System check System information Water pressu...

Page 50: ...ses flammable gas may be mixed in so when venting keep ignition sources away and ventilate well User In order to ensure optimal performance of the units user may inspect and clear any obstruction on t...

Page 51: ...er time to heat up System does not heat up instantly System will take some time to heat up the water if it starts to operate at cold water temperature Backup heater is automatically turned ON when it...

Page 52: ...rror No Error explanation F12 Pressure switch activated F14 Poor compressor rotation F15 Fan motor lock error F16 Current protection F20 Compressor overload protection F22 Transistor module overload p...

Page 53: ...t phone device to prevent miss operation Do not use other remote control communication and operation device not specified by an authorised dealer or specialist Use under the agreement of Terms of Serv...

Page 54: ...gether with an external ignition source there is a possibility of fire explosion This symbol shows that the Operation Instructions should be read carefully This symbol shows that a service personnel s...

Page 55: ...untry Hotline Phone Number Country Hotline Phone Number Austria 0800 700666 Hungary 36 1 382 60 60 Baltic 46 8 680 26 50 Netherlands 31 0 736402538 Bulgaria 359 2 971 29 69 Norway 47 210 339 99 Croati...

Reviews: