Specifications
© Panasonic Industrial Devices SUNX Co., Ltd. 2017
146
Type
10mm pitch type
20mm pitch type
40mm pitch type
Model No.
SF4D-F
□
SF4D-H
□
SF4D-A
□
Vibration resistance
10 to 55Hz, 0.75mm double amplitude for two hours each in X, Y, and Z directions
Malfunction resistance 10 to 55Hz, 0.75mm double amplitude 20 times each in X, Y, and Z directions
Shock resistance
300m/s
2
(approx. 30G) 3 times each in X, Y, and Z directions
Malfunction resistance 100m/s
2
(approx. 10G) 1,000 times each in X, Y, and Z directions
SFF
(Safe Failure Fraction)
99%
HFT (Hardware Fault
Tolerance)
1
Subsystem type
Type B (IEC 61508-2)
T1 (proof test interval)
20 years
Failure response time
Within response time (OFF response)
Safety state
Control output (OSSD 1 / 2) OFF state
Emitter element
Infrared LED (peak emission wavelength: 850nm)
Connection method
By connector
Cable extension
Total length of emitter / receiver can be extended up to 70m each using optional con-
nection cable (Note 5)
Material
Enclosure: Aluminum, Detection surface: Polycarbonate / resin and SS304
Upper cap / lower cap: Nylon
Accessories
SF4B-TR14
(test rod): 1 pc.
SF4B-TR25
(test rod): 1 pc.
−
Applicable standards
IEC 61496-1/2 (Type 4), ISO 13849-1: 2015 (Category 4, PLe), IEC 61508-1 to 7 (SIL3)
EN 61496-1/2 (Type 4), EN ISO 13849-1: 2015 (Category 4, PLe), EN 55011
EN 61000-6-2, EN 50178, JIS B 9704-1/2 (Type 4), JIS B 9705-1 (Category 4)
JIS C 0508-1 to 7 (SIL3), ANSI/UL 61496-1/2 (Type 4), CAN/CSA C22.2 No.14
CAN/CSA E61496-1/2
Notes: 1) The setting can be changed using the communication module
SF4D-TM1
(option) and Configurator
Light Curtain software.
2) Because the control output (OSSD 1 / 2) must be OFF for at least 80ms, the ON response will be de
-
layed more than 50ms when the light blocked time is less than 30ms.
3) When optical synchronization is selected, if the beam axes of both the top end and bottom end are
blocked, the ON response speed decreases by as much as 1 sec.
4)
Do not use or store in an environment pressurized to atmospheric pressure or higher at an altitude of 0m.
5) Taking cable voltage drop and other factors into account, use a cable length as indicated below for the
source / sink current of the control output (OSSD 1 / 2).
Number of sub-
sensors
Control output (OSSD 1
/ 2) source / sink current
Length of power cable
+ length of series
connection cable
(total cable length)
Cable
Length of power cable
Length of series
connection cable
0
(no series connection)
100mA
70m or less
-
-
200mA
70m or less
-
-
350mA
10.5m or less
-
-
1
100mA
50m or less
-
Total cable length
minus the power
cable length
200mA
50m or less
-
350mA
50m or less
10.5m or less
2
100mA
50m or less
-
200mA
50m or less
-
350mA
50m or less
10.5m or less
3
100mA
50m or less
-
200mA
50m or less
40.5m or less
350mA
50m or less
10.5m or less
4
100mA
25.5m or less
-
200mA
25.5m or less
20.5m or less
350mA
25.5m or less
10.5m or less
Power cable: A bottom cap cable (option) combined with an extension cable (option)
Summary of Contents for WUME-SF4D-4
Page 2: ... Panasonic Industrial Devices SUNX Co Ltd 2017 2 MEMO ...
Page 126: ...Functions Panasonic Industrial Devices SUNX Co Ltd 2017 126 MEMO ...
Page 130: ...Maintenance Panasonic Industrial Devices SUNX Co Ltd 2017 130 MEMO ...
Page 140: ...Troubleshooting Panasonic Industrial Devices SUNX Co Ltd 2017 140 MEMO ...
Page 174: ... Panasonic Industrial Devices SUNX Co Ltd 2017 174 MEMO ...