PDU INSTALLATION MANUAL
Before You Begin
Overview
This document provides installation instructions and configuration instructions to
qualified personnel for installing a Panduit Metered, Switched, and Metered &
Switched Power Distribution Unit (PDU) into a datacenter rack. Please read all
instructions before operating the equipment and save this manual for future
reference.
Important Safety Information
See the complete regulatory compliance notices in Safety and Compliance Information
for Server, Storage, Power, Networking, and Rack Products on the Panduit website
(http://www.panduit.com/). In addition, follow the safety precautions that are specific to
this device.
This PDU is intended only for Information Technology Equipment (ITE) loads with
linear/Power Factor Corrected (PFC) input current. If non-linear loads are connected,
the nameplate current rating of the PDU must be reduced by a factor of 0.8.
WARNING:
A risk of personal injury from electric shock and hazardous energy
levels exists. The installation of options and routine maintenance and service of this
product must be performed by individuals who are knowledgeable about the
procedures, precautions, and hazards associated with AC power products.
IMPORTANT SAFETY INSTRUCTIONS-----SAVE THESE INSTRUCTIONS
Follow these safety precautions when connecting multiple hardware
components to power sources
WARNING:
To reduce the risk of fire, electric shock and damage to the
equipment:
HIGH LEAKAGE CURRENT.
To reduce the risk of electric shock due to high
leakage currents, ensure that there is a reliable grounded (earthed)
connection before connecting power distribution products to AC power. If a