For Technical Support: www.panduit.com/resources/install_maintain.asp

INSTALLATION INSTRUCTIONS

 © Panduit Corp. 2010

FS012

After the enclosure is mounted in the rack, determine 
the size of the innerduct that will be used to bring the 
cable into the enclosure. Install grommet following 
the proper cutting diagram (See Figure 4A).

Cut the small circle 
for 1" diameter 
innerduct

Cut the large circle 
for 1-1/2" diameter 
innerduct

Cut the straight 
lines when not 
using any 
innerduct

Install the strain relief bracket near where the 
cable will enter the enclosure. Secure with a 
#10-32 x 3/8" screw and #10-32 hex nut.

Strain Relief Bracket

#10-32 x 3/8" Screw

#10-32 Hex Nut

Figure 4A

Figure 4B

Figure 5

Page 3 of 10

Grommet

Summary of Contents for FCE4U

Page 1: ...NG UNMATED CONNECTORS MAY EMIT INVISIBLE LASER RADIATION DO NOT LOOK DIRECTLY INTO THE END OF THE CONNECTOR DO NOT INSPECT WITH MAGNIFYING DEVICES MAINTAIN CAP ON UNMATED CONNECTORS Care should be tak...

Page 2: ...surrounding sheet metal DO NOT install grommet at this stage grommet will be installed after enclosure is mounted to rack Place enclosure mounting brackets at desired position on the rack Mount the en...

Page 3: ...re Install grommet following the proper cutting diagram See Figure 4A Cut the small circle for 1 diameter innerduct Cut the large circle for 1 1 2 diameter innerduct Cut the straight lines when not us...

Page 4: ...lted down cables omitted for clarity Opticom QuickNet Cassette Installation Route fiber through grommet to fiber cassettes as shown Leave enough slack so when the drawer is fully extended the cables a...

Page 5: ...For Technical Support www panduit com resources install_maintain asp INSTALLATION INSTRUCTIONS Panduit Corp 2010 FS012 Figure 6C Tray in home position cover omitted for clarity Page 5 of 10...

Page 6: ...punch hole into adhesive mounts Note spool orientation Position FAPs between upright flanges as shown Once mounted fully seat NyLatches to secure FAPs Fully extend tray to ensure proper amount of slac...

Page 7: ...tended the cables are not put under tension DO NOT use so much slack that the drawer cannot be returned to its home position See Figure 7C Use Tak Tys to secure fiber cords at cable entry location and...

Page 8: ...der note orientation The remaining FOSMs are stacked on top of each other and snap in place after termination of lower tray Position FAPs between upright flanges as shown Once mounted fully seat NyLat...

Page 9: ...lete loop of individual fibers around splice tray slack spools See instruction sheet for splice trays Leave enough jacketed slack so when the drawer is fully extended the cables are not put under tens...

Page 10: ...eld to allow room to route patch cords under the tabs to the cable manager Plug fiber connector into FAP adapter Route patch cords down to fiber manager base under fiber manager fingers and Bend Radiu...

Reviews: