FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp
INSTRUCTIONS CM227
© Panduit Corp. 2006
Page 1 of 2
P
AN
Z
ONE
Under Floor Enclosures
Part Numbers: CIFZC4, CIFZC8, CIFZC11, CIFZC4F, CIFZC6F
Part Number
CIFZC4
CIFZC8
CIFZC11
CIFZC4F
CIFZC6F
Required Minimum Floor Depth
6"
8"
14"
10"
14"
The following items are included.
Required Tools
Installation:
(for floors with stringers)
Figure 1
CIFZC4
CIFZC8
7/16” Open End Wrench
1/2” Open End Wrench
Phillips Head Screw Driver
Slotted Screw Driver
(1) Foam Kit
(4) Leveler Bolts
(4) Support Brackets, with
Washers and Nuts
(2 or 4) Cable
Entry Port Covers
(1) Enclosure
Installation
Location
Figure 2
1. Select the installation location ensuring there are no obstacles to
interfere with the installation.
2. Remove five tiles from the floor in the shape of a “+” (See Figure 2).
3. Remove the two adjacent stringers that run between the supports
CIFZC4F
CIFZC6F
CIFZC11
Figure 3
Mounting Bracket for Patch Panel
Leveler
Bolt
Cable Entry
Port Cover
Foam Sheets
Stanchion
Support Bracket with
Washers and nuts
Enclosure
(CIFZC8 Shown)