SMARTZONE UPS USER MANUAL
19
NEMA 5-15P plug. These units have two groups of outlets. For the 2kVA VRLA UPS
unit Group 1 (4x 5-20R) outlets are the main outlets that are not switchable, and Group
2 (2x 5-20R) are switchable outlets. For the 1.5kVA Li UPS unit Group 1 (4x 5-15R)
outlets are the main outlets that are not switchable, and Group 2 (2x 5-15R) are
switchable outlets. Group 1 outlets should contain the critical loads and Group 2 outlets
could contain the non-critical loads. When the UPS is operating in the battery state,
Group 2 outlets may be programmed to turn off earlier to conserve battery capacity for
the Group 1 outlets.
Figure 6
:
2kVA VRLA NA Rear Panel View (U02x11V)
Figure 7
:
1.5kVA Li NA Rear Panel View (U02x11L)
3kVA North America Model Rear Panels (U03x11V / U03x11L)
The 3kVA NA UPS units have a permanently connected input power cord with a NEMA
L5-30 plug. These units have two groups of outlets. Group 1 (2x 5-20R and 1x L5-30R)
outlets are the main outlets that are not switchable. These outlets should contain the
critical loads. Group 2 (2x 5-20R) outlets are switchable. These outlets could contain the
non-critical loads. When the UPS is operating in the battery state, Group 2 outlets may
be programmed to turn off earlier to conserve battery capacity for the Group 1 outlets.