SMARTZONE UPS USER MANUAL
44
Screen #
DC Li Settings
Content display
S-04
Group 2 Battery EOD setting
(000, 020, 030)
Group 2 is the switchable outlet group. This outlet group may be utilized to power
non-critical loads. The default Group 2 Battery End of Discharge (EOD) setting is
0%. This group of outlets may be configured to turn OFF before the Group 1
outlets. This setting is the percentage of battery capacity left when the outlet group
turns OFF. The lower the percentage setting, the longer outlet Group 2 will stay
ON while the UPS is running on battery. However, the longer this outlet group
stays ON, the less runtime there is for outlet Group 1, which may contain the
critical loads. If all outlets are used for critical loads, then set Group 2 capacity
equal to the Group 1 at 0%.
S-05
Bypass Voltage Upper Limit
setting
(230 – 264)
The default Bypass Voltage Upper Limit setting is 264Vac for European UPS units.
These values my be changed in 1Vac increments/decrements. This value should
be set to the maximum voltage that the connected loads will tolorate. Decreasing
this voltage may limit the UPS from switching to bypass (when the input voltage is
high).