SMARTZONE UPS USER MANUAL
45
Screen #
DC Li Settings
Content display
S-06
Bypass Voltage Lower Limit
setting
(176 – 220)
The default Bypass Voltage Lower Limit setting is 176Vac for European UPS units.
These values my be changed in 1Vac increments/decrements. This value should
be set to the minimum voltage that the connected loads will tolorate. Increasing
this voltage may limit the UPS from switching to bypass (when the input voltage is
low).
S-07A
Buzzer setting
(ON, OFF)
The default Buzzer setting is ON.
S-07B
Buzzer setting
(ON, OFF)
To mute all audiable alarms set this to OFF. The Buzzer will be muted, even with
new Alerts. A speaker with a line through it, will be illuminiated in the upper right
corner of all pages.