SMARTZONE UPS USER MANUAL
50
26
Battery Over Voltage
Warning
Periodic
Yellow Alert
On
Ensure that the EBP and
battery cartridge match
the UPS battery voltage.
27
Input Voltage Reversed
Warning
Periodic
Yellow Alert
On
Ensure that the input
source Line and Neutral
are not reversed.
28
Bypass Voltage Reversed
Warning
Periodic
Yellow Alert
On
Ensure that the input
source Line and Neutral
are not reversed.
29
Output Short-circuit
Warning
Periodic
Yellow Alert
On
Remove the loads and
add back one at a time
to detect load that is
short-circuited.
30
Input Current Limit
Warning
Periodic
Yellow Alert
On
Reduce the output load.
31
Bypass Over Current
Warning
Periodic
Yellow Alert
On
Reduce the output load.
32
Output Overload
Warning
Periodic
Yellow Alert
On
Reduce the output load.
33
No Battery Detected
Warning
Periodic
Yellow Alert
On
Ensure that the battery
connector is properly
seated and making a
good connection.
Allow the Battery to
recharge.
34
Battery Depleted
Warning
Periodic
Yellow Alert
On
Allow battery to
recharge.
35
Battery Low
Warning
Periodic
Yellow Alert
On
Allow battery to
recharge.
36
Output Overload Time Out
Warning
Periodic
Yellow Alert
On
Reduce the output load.
37
DC Component Over Limit
Error
Critical Continuous Red Alert On Reboot the UPS unit.
39
Input Voltage Abnormal
Warning
Periodic
Yellow Alert
On
Ensure that the source
input voltage is within
the UPS operating
range.
40
Input Frequency Abnormal
Warning
Periodic
Yellow Alert
On
Ensure that the source
input frequency is
within the UPS
operating range.
41
Bypass Not Available
Warning
Periodic
Yellow Alert
On
Ensure that the source
input voltage and
frequency are within the
UPS operating range.