SMARTZONE UPS USER MANUAL
55
UPS Operating State
Range
Comments
Normal or Gen state
Voltage Range
100Vac: 90 ~ 110Vac
110Vac: 99 ~ 121Vac
115Vac: 104 ~ 126Vac
120Vac: 108 ~ 132Vac
125Vac: 113 ~ 137Vac
If the input voltage goes outside of
this range, the UPS will transition to
the AVR state.
AVR state Voltage
Range
100Vac: 75 ~ 93(Boost)/107 ~ 117(Buck)
110Vac: 83 ~ 103(Boost)/117 ~ 133(Buck)
115Vac: 86 ~ 107(Boost)/123 ~ 139(Buck)
120Vac: 90 ~ 112(Boost)/128 ~ 145(Buck)
125Vac: 94 ~ 117(Boost)/133 ~ 151(Buck)
If the input voltage goes above the
Boost range and below the Buck
range, then the UPS will transition
back to the Normal or Gen state.
If the input voltage goes below the
Boost range or above the Buck range,
then the UPS will transition to the
Battery state.
CF, ECO Mode Voltage
Range
NA
NA
Normal state Frequency
Range
50/60 ±4Hz
If the input frequency goes outside of
the this range, the UPS will transition
to the Battery state.
Gen state Frequency
Range
40 ~ 70Hz
If frequency is with in the range, the
frequency variation will get passed to
the load.
If the frequency goes outside of this
range, the UPS will transition to the
Battery state.
CF, ECO Mode
Frequency Range
NA
NA
Normal, Gen, or Battery
state Overload
105% ~ 110%: overload alarm indefinitely;
110% ~ 120%: 10 secs;
>120%: 0 secs;
Overload Alarm for time specified and
then the UPS will shutdown.
1-3kVA Line Interactive