SMARTZONE UPS USER MANUAL
100
UPS Operating State
Range
Comments
Normal or CF state
Voltage Range
Full load: 305 ~ 485 Vac
40% load: 138 ~ 485 Vac
If the input voltage goes outside of the range,
the UPS will transition to Battery state.
ECO state Voltage
Range
220Vac: 209 ~ 231Vac
230Vac: 219 ~ 241Vac
240Vac: 228 ~ 252Vac
If the input voltage goes outside of the settable
range, the UPS will transition to the Normal
state.
ECO Mode while in
the Normal State
Voltage Range
220Vac: 214 ~ 226Vac
230Vac: 224 ~ 236Vac
240Vac: 233 ~ 247Vac
If the input voltage goes
inside
the settable
range, the UPS will transition back to ECO state.
Bypass state Voltage
Range
220Vac: +10%,+15%,+20%, +25% (settable)
230Vac: +10%,+15%, +20% (settable )
240Vac: +10%, +15% (settable )
Min. voltage: -10%,-15%,-20%,-30%, -45% (settable)
If the input voltage goes outside of the settable
range, the UPS will shut down.
Gen Mode Voltage
Range
There is no Gen Mode selection
There is no Gen Mode selection
Normal state
Frequency Range
40 ~ 70Hz
If the input frequency goes outside of this
range, the UPS will transition to the Battery
state.
CF state Frequency
Range
40 ~ 70Hz
If the input frequency goes outside of this
range, the UPS will transition to the Battery
state.
ECO or Bypass state
Frequency Range
50/60 ±1%/2%/4%/5%/10%(settable)Hz
If the input frequency goes outside of the
settable range, the UPS will transition to the
Normal state and then fix the output frequency
at 50Hz or 60Hz.
Gen Mode Frequency
Range
There is no Gen Mode selection becuause the UPS always
operates with the wider input frequency range.
There is no Gen Mode selection becuause the
UPS always operates with the wider input
frequency range.
Normal state
Overload
105% ~ 110%: 60 mins;
110% ~ 125%: 10 mins;
125% ~ 150%: 1 min;
>150%: 500 msecs;
Overload Alarm for time specified and then the
UPS will transition to the Bypass state.
CF state Overload
105% ~ 110%: 60 mins;
110% ~ 125%: 10 mins;
125% ~ 150%: 1 min;
>150%: 500 msecs;
Overload Alarm for time specified and then the
UPS will shutdown.
Battery state Overload
105% ~ 110%: 60 mins;
110% ~ 125%: 10 mins;
125% ~ 150%: 1 min;
>150%: 500 msecs;
Overload Alarm for time specified and then the
UPS will shutdown.
ECO or Bypass State
Overload
≤130%: overload alarm indefinitely;
130% ~ 150%: 10 mins;
150% ~ 200%: 1 mins;
>200%: 1 secs;
10x the rated current: 100 msecs;
Overload Alarm for time specified and then the
UPS will shutdown.
Gen Mode Overload
There is no Gen Mode selection.
There is no Gen Mode selection.
10-20kVA Double Conversion