SMARTZONE UPS USER MANUAL
62
(1.75V, 1.84V, or 1.92V) at which Outlet Group 2 will automatically turn OFF. The
default is 1.75V, which is the same voltage that the Group 1 outlets will turn OFF when
running in battery mode. A higher cell voltage will turn OFF the outlet group sooner and
allow longer runtime on the critical loads that may be connected to Outlet Group 1.
Press the left or right arrows in the GROUP3 EOD (V/Cell) line to select the cell voltage
(1.75V, 1.84V, or 1.92V) at which Outlet Group 3 will automatically turn OFF. The
default is 1.75V, which is the same voltage that the Group 1 outlets will turn OFF when
running in battery mode. A higher cell voltage will turn OFF the outlet group sooner and
allow longer runtime on the critical loads that may be connected to Outlet Group 1. This
is supported only on the EU Single-Phase 6-10kVA UPS units (U06N12V, U06S12V,
U10N12V, and U06S12V); this line is not present on the NA Single-Phase 5-10kVA
single-phase UPS units (U05N11V, U05S11V, U06N11V, U06S11V, U10N11V, and
U10S11V).
After making all the necessary changes on this page, press the “Save Config” button to
save the changes.
Press the down arrow to go to the next battery setup page. Press the up arrow to go to
the previous battery setup page. Press the up and over arrow to return to the Advanced
Setup Menu page.
Figure 48: Battery Setup Page 3 (Single-Phase UPS)
On the Battery Installed Date line, press the number in front of the Year to type in the
install year. Press the number in front of the Month to type in the install month. Press
the number in front of the Day to type in the install day. The default values for the year,
month and day are based on when the battery was fully charged at build time. It may