SMARTZONE UPS USER MANUAL
101
Appendix D: Maintenance and Storage
Maintenance
The repair and replacement of any components in the UPS system must be performed by
qualified personnel. If the battery cartridge has exceeded its service life (about 3-5 years at
25°C), contact Panduit Sales for qualified replacements. Refer to the SmartZone UPS Installation
Manual for details on replacing the battery cartridges.
•
•
•
Storage/Transportation
Before storing or transporting the UPS or EBP units with battery cartridges or replacement
battery cartridges, charge the cartridge for 5 hours with no load. Disconnect the battery
cartridge(s) from the system (see the SmartZone UPS Installation Manual). Store/transport the
product in the upright orientation in normal packaging in a dry environment. During storage,
recharge and maintain according to the following table:
Storage
temperature
Charging interval
Charging time
-25°C - 40°C
Every 3 months
1-2 hours
40°C - 45°C
Every 2 months
1-2 hours
Note:
Environmental factors affect battery life. High ambient temperature, high humidity, low-
voltage, and frequent, short-term discharges will shorten the battery life.
Used battery cartridges should be properly disposed per local
regulations. Refer to the Panduit Support Website at:
https://www.panduit.com/en/support/ups-battery-recycling.html