SMARTZONE UPS USER MANUAL
102
Appendix E: Configuration Options
The following options should be configured on a newly installed UPS System. These are
the minimum options that should be configured after initial power up of the system.
Other options could be configured later. However, if the system being powered up is a
parallel system, then the parallel configurations must also be configured at initial power
up. Please refer to the
Mode Setup and Startup” section under Basic
Operations for the procedures for starting up a parallel system.
Display
Menu Path
Parameters
Default
Value
Options
Description
Setup/
Basic
Language
English
English,
Simplified
Chinese
Select the language required for the UPS
Display Interface.
Language options vary by model and
firmware version.
Password
123456
6 digits
The password must be 6 characters,
numbers only. For security, this
password must be change after initial
power up.
Date & Time 2022-01-01 &
07:00:00
YYYY-MM-DD,
HH:MM:SS
Enter the current date and time (
Note:
time is 24-hour format).
Setup/
Advanced
Output Setup
Depends on
SKU
(NA = 208V,
EU = 230V)
Depends on
SKU
Set the output voltage for the UPS. This
setting can only be changed when the
UPS output is off.
Configure these settings at any time, using the UPS Display Interface or the Web UI.
Display
Menu Path
Parameters
Default
Value
Options
Description
Setup/
Basic
Language
English
English,
Simplified
Chinese
Select the language required for the UPS
Display Interface.
Language options vary by model and
firmware version.
Password
123456
6 digits
The password must be 6 characters,
numbers only.
Display
Brightness
63
10–63
Set the brightness of the display (10-63).
Display
Backlight
Timeout
60 secs
10-255 secs
To conserve energy, the LCD back light
illumination turns off with no activity after
this time.