SMARTZONE UPS USER MANUAL
103
Full UPS Display Interface illumination
returns when the UPS changes status
because of an event or when the UPS
Display Interface is pressed.
Date & Time
2022-01-01 &
07:00:00
YYYY-MM-DD,
HH:MM:SS
Enter the current date and time (
Note:
time is 24-hour format).
Setup/
Advanced/
System
Setup
Working Mode
Normal
Normal, ECO,
CF, Generator
Set up the UPS working mode (Gen
mode on single-phase only).
System
Configuration
Single
Single,
Parallel
Single means a single UPS in the
system.
Parallel means 2 to 4 UPSs in a system
(available only on the 3-Phase UPS).
Input: Output
Phase
3:3
3:3,
3:1
3-Phase IN and 3-Phase OUT or 3-
Phase IN and single-Phase OUT
(available only on the 3-Phase UPS).
Setup/
Advanced/
Parallel
Setup
(3-phase
units only)
Parallel ID
1
1, 2, 3, 4
Each UPS in a parallel system must have
a unique ID.
Parallel Basic
Units
2
2, 3, 4
This is the number of UPS units in the
system.
Parallel
Redundancy
Units
0
0, 1, 2. 3
When the parallel system is setup for a
redundancy parallel configuration, this is
the number of redundant UPS units in
the system (0 means no redundancy).
Setup/
Advanced/
Output
Setup
Output
Frequency
Auto
Auto,
50Hz, 60Hz
Set the output frequency for the UPS.
Output
Voltage
Depends on
SKU
(NA = 208V,
EU = 230V)
Depends on
SKU
Set the output voltage for the UPS. This
setting can only be changed when the
UPS output is off.
Inverter
Voltage
Adjustment
0.0%
-5% to +5%
(Increments of
0.5%)
Used for fine tuning the output on UPS
units in the parallel system (available
only on the 3-Phase UPS).
Setup/
Advanced/
Battery
Setup
Battery Group
1
1 to 5
or
1 to 8
Set the number of EBP units connected
to the UPS (single-phase UPS is 1-5 and
3-Phase UPS is 1-8).
Boost/Float
Conversion
0 Months
0 to 24
Used for battery life optimization
(available only on the 3-Phase UPS).
Cell Float
Voltage
2.25V
2.20-2.29V
Used for battery life optimization
(available only on the 3-Phase UPS).
Cell Boost
Voltage
2.35V
2.30-2.40V
Used for battery life optimization
(available only on the 3-Phase UPS).
Boost Charge
Setting
Enable
Enable, Disable
Used for battery life optimization
(available only on the 3-Phase UPS).
No Battery
Enable
Enable, Disable Allows warning to be disabled when