SMARTZONE UPS USER MANUAL
104
Warning
there is no battery connected to the UPS.
Shared Battery
Disable
Enable, Disable
For parallel system, this allows the
charging circuit in multiple UPS units to
charge the batteries in the system
(available only on the 3-Phase UPS).
EOD Group 2
1.75
1.75, 1.84, 1.92
Set Group 2 outlets to a battery cell
voltage that will cause the outlets to
automatically turn off when the UPS is in
the battery state (available only in single-
phase UPS units).
EOD Group 3
1.75
1.75, 1.84, 1.92
Set Group 3 outlets to a battery cell
voltage that will cause the outlets to
automatically turn off when the UPS is in
the battery state (available only in single-
phase EU UPS units).
Install Date
Date Built
Year, Month,
Day
This setting will set the start date to
determine when the battery notification
and alarm will activate. Incorrect entries
will default to 1.
Replacement
Notification
372 days
0 - 730
This is the number of days prior to 3
years (1095 days) that the battery
replacement notification will be activated.
This notification should be set to allow for
a new battery to be ordered and replaced
before the battery replacement alarm is
activated.
Replacement
Alarm
365 days
0 - 365
This is the number of days prior to 3
years (1095 days) that the battery
replacement alarm will be activated. This
alarm should be set based on your
company’s policies for replacing UPS
batteries. The expected life of a VRLA
battery is 3 years, but your company’s
policy may be shorter than this.
Setup/
Advanced/
Bypass
Setup
Voltage Lower
Limit
Based on
SKU
(NA S-P=
-15%,
EU S-P =
-20%,
EU 3-P =
-15%)
-25%, -20%,
-15%, -10%,
-5%
Set the acceptable bypass lower limit
voltage represented as a percentage of
the nominal input voltage.
Note:
This
should be set based on the loads input
voltage range.
Voltage
Upper Limit
Based on
SKU
(NA S-P=
15%,
EU S-P =
10%, 15%,
20%, 25%
Set the acceptable bypass upper limit
voltage represented as a percentage of
the nominal input voltage.
Note:
This
should be set based on the loads input
voltage range.