SMARTZONE UPS USER MANUAL
10
If an internal or external event occurs while operating in the normal state, the UPS will
automatically transition to battery, bypass, fault, or battery test state depending on the
event.
ECO State
The UPS will go into the ECO state when the UPS is set to ECO Mode at setup time. If
the UPS is set for ECO Mode, the ECO state is the default state where the UPS will
return to after the internal or external event has been cleared or the forced state has
expired.
If an internal or external event occurs while operating in the ECO state, the UPS will
automatically transition to normal, battery, fault, or battery test state depending on the
event.
CF State
The UPS will go into CF state when the UPS is set to CF Mode at setup time. If the UPS
is set for CF Mode, the CF state is the default state where the UPS will return to after
the internal or external event has been cleared or the forced state has expired.
If an internal or external event occurs while operating in the CF state, the UPS will
automatically transition to battery, bypass, fault, or battery test state depending on the
event.
Gen State
The UPS will go into Gen state when the UPS is set to Generator Mode at setup time. If
the UPS is set for Generator Mode, the Gen state is where the UPS will return to after
the internal or external event has been cleared or the forced state has expired.
If an internal or external event occurs while operating in the Gen state, the UPS will
automatically transition to battery, bypass, fault, or battery test state depending on the
event.
Battery State
The UPS automatically transitions to the Battery state with no power interruption to the
load when input power is out of the set range or power is lost. The UPS will
automatically return to the default state when the input source recovers.
If an internal or external output event occurs while operating in the Battery state, the
output will shut down. AC power to the load will be lost.
Bypass State
The UPS may automatically transition to the Bypass state with no power interruption