SMARTZONE UPS USER MANUAL
110
o
This input dry contact setting is used with a customer added input bypass
breaker that has trip sensing capabilities. This will present an alarm when
the breaker is tripped.
•
BATT Switch
•
This input dry contact setting is used with a customer added battery breaker that
has position sensing capabilities. This will present an alarm when the breaker
position is open.
•
BATT Trip
o
This input dry contact setting is used with a customer added battery
breaker that has trip sensing capabilities. This will present an alarm when
the breaker is tripped.
•
BATT Ground
•
This input dry contact setting is used with a customer added ground sensing
device that sense when the ground is not connected. This will present an alarm
when the ground is not connected to the EBP.
•
Thunder
o
This input dry contact setting is used with a customer added lightning
detection device that sense when a lightning strike has occurred. This will
present an alarm when a lightning strike has been detected.
•
EPO
•
This input dry contact setting is used with a customer added emergency power
off device that triggers when the device is activated. This will present an alarm
when the EPO device has been activated. This setting could be used in addition
to or instead of the EPO dedicated port on the back of the UPS.
Output Dry Contact Assignments:
•
Close
o
The dry contact is unassigned.
•
UPS Warning
o
When activated the UPS is indicating the UPS has a warning or critical
alarm. This is an aggregation of all alarms.
•
Online Mode
o
When activated the UPS is indicating it is operating in the Normal state.
•
Battery Mode
o
When activated the UPS is indicating it is operating in the Battery state.
•
Bypass Mode
o
When activated the UPS is indicating it is operating in the Bypass state.
•
INV Overload
o
When activated the UPS is indicating it has detected an output Overload.
•
Fan Fault
o
When activated the UPS is indicating it has detected an internal fan fault.