SMARTZONE UPS USER MANUAL
22
U06N12V / U06S12V / U10N12V / U10S12V
The 6 and 10kVA EU UPS units have a terminal block for a hardwire connection on the
input of the UPS. These units have three groups of outputs. Group 1 (hardwire
connection) is the main non-switchable output. This output should contain the critical
loads. Group 2 (2x C-13 with a 10A output breaker) are switchable outlets. These
outlets may be used for non-critical loads. Group 3 (2x C-19 with a 16A output breaker)
are switchable outlets. These outlets may be used for non-critical loads. When the UPS
is operating in the battery state, Group 2 and 3 outlets may be programmed to turn off
earlier to conserve battery capacity for the Group 1 output.
4. Intelligent Slot
10. Group 2 Breaker
16. Input Breaker
5. Maint. Bypass Signal 11. Group 2 Outlets
17. Input Power Terminals
6. EPO Signal Port
12. Group 3 Outlets
18. Ground Screw
7. USB Coms Port
13. Group 3 Breaker
8. DB9 Coms Port
14. EBP Connector
9. Battery Temp. Port
15. Group 1 Terminals
Figure 6: European 6 and 10kVA Rear View (U06x12V / U10x12V)