SMARTZONE UPS USER MANUAL
47
of the UPS (where the air enters the UPS from the cold aisle). The Ambient
Temperature is measured with a temperature sensor and is displayed on this page.
Press the up arrow to go to the previous Status Information page. Press the up and over
arrow to return to the Status Menu page.
Battery Status Page
These two pages provide the status of the battery connected to the UPS.
Note:
All references to battery in this section refer to all EBP units connected to the system as
one battery.
Figure 27: Battery Status Page 1 (Single-Phase UPS)
The first page contains the battery voltage, battery current, battery status, and ambient
temperature in the first connected EBP unit.
Note:
The voltage and current are shown for the positive battery and the negative battery as
described in
of this document. The overall battery voltage and
current is the sum of the two absolute numbers (the 5-10kVA single-phase UPS unit’s voltage is
in the range of 240V and the 10-20kVA 3-phase UPS unit’s voltage is in the range of 480V).
Note:
It is assumed that all EBP units connected to the UPS are in the same environment. The
battery temperature on this page is the battery temperature in the first EBP connected to the UPS.
Press the down arrow to go to the next Battery Status page. Press the up and over
arrow to return to the previous page, the Status Menu page, or Home Page depending
on operations used to get to this page.